Download BTRM200 User Guide

Transcript
VENTEV INNOVATIONS BTRM200 Battery Test Remote Monitoring System – User Guide V1.0
To clear or enable write a "1", or to disable write a "0".
An xample to reset battery data, g10v01 q00 start 0 stop 0 value 1, would be to issue
an application layer write command of the form:
c5 02 0a 01 00 00 00 01
Point
0
1
2
3
Description
Battery Data Reset
Battery LV Disconnect Enable
Battery Test Enable
Battery Start / Stop Test
State
Write to Enable
Write to Clear
Write to Start
Write to Start
Value
0x81
0x81
0x81
0x81
State
Write to Disabled
Cleared
Write to Stop
Write to Stop
Value
0x01
0x01
0x01
0x01
9.1.3.9. Events
When Events are generated, they are reported via unsolicited messaging (if
enabled), or queue to the event list for reading when polling for Class 2 data, or
reading Binary events. Event points correspond to Binary Input Points.
Point
1
2
4
5
Description
Low Battery Capacity Event
Low Battery Voltage Event
Aux IO Channel 1 Event
Aux IO Channel 2 Digital In
9.1.3.10.
9.2. Mod Bus
- expected Q3/2013
48
State
Tripped Event
Tripped Event
Tripped Event
Tripped Event
Value
0x81
0x81
0x81
0x82