Download Series 90
Transcript
Series 90-30 Strain Gage I/O Modules The Millivolt Input Modules allow millivolt level signals, such as bridged strain gages (load cells) to be directly connected to the PLC without external signal processing (transducers, transmitters, etc.) All analog and digital processing of the signal is performed on the module. HE693STG883 HE693STG884 Analog I/O Module, Strain Gage Analog I/O Module, Strain Gage Strain Gage Input Strain Gage Input Input Voltage Range ±20 mV, ±25 mV and ±30mV ±25 mV, ±50 mV and ±100mV Number of Channels 8 8 Resolution 0.6 µV, 0.8 µV, 0.9 µV (respectively) 0.8 µV, 1.6 µV, 3.2 µV (respectively) Accuracy ±0.3% ±0.3 % >1000 Mohms >1000 Mohms A/D Conversion Type Integrating Integrating A/D Conversion Time 35 Channels/second 35 Channels/second Bridged (load cells) Bridged (load cells) 100 mV 100 mV ±35 V ±35 V Terminal Block (20 screws), included with module. Terminal Block (20 screws), included with module. 60 mA @ 5 VDC; 30 mA @ 24 VDC Relay 60 mA @ 5 VDC; 30 mA @ 24 VDC Relay Product Name Module Type Input Impedance Strain Gages Supported Maximum Normal Voltage Input Maximum Voltage Input Connector Type Internal Power Used www.ge-ip.com GE Intelligent Platforms Control Systems Solutions 141