Download Series 90

Transcript
Series 90-30
Strain Gage I/O Modules
The Millivolt Input Modules allow millivolt level signals, such as bridged strain gages
(load cells) to be directly connected to the PLC without external signal processing
­(transducers, transmitters, etc.) All analog and digital processing of the signal is
performed on the ­module.
HE693STG883
HE693STG884
Analog I/O Module, Strain Gage
Analog I/O Module, Strain Gage
Strain Gage Input
Strain Gage Input
Input Voltage Range
±20 mV, ±25 mV and ±30mV
±25 mV, ±50 mV and ±100mV
Number of Channels
8
8
Resolution
0.6 µV, 0.8 µV, 0.9 µV
(respectively)
0.8 µV, 1.6 µV, 3.2 µV
(respectively)
Accuracy
±0.3%
±0.3 %
>1000 Mohms
>1000 Mohms
A/D Conversion Type
Integrating
Integrating
A/D Conversion Time
35 Channels/second
35 Channels/second
Bridged (load cells)
Bridged (load cells)
100 mV
100 mV
±35 V
±35 V
Terminal Block (20 screws),
included with module.
Terminal Block (20 screws),
included with module.
60 mA @ 5 VDC; 30 mA @ 24 VDC
Relay
60 mA @ 5 VDC; 30 mA @ 24 VDC
Relay
Product Name
Module Type
Input Impedance
Strain Gages Supported
Maximum Normal Voltage Input
Maximum Voltage Input
Connector Type
Internal Power Used
www.ge-ip.com