ACS 140 Basic Parameters
ACS 140 has a large number of parameters. Of these, only the so called
basic parameters are initially visible.
Setting up only a few basic parameters is sufficient in applications where the
preprogrammed application macros of the ACS 140 can provide all desired
functionality. For a full description of programmable features provided by the
ACS 140, see “ACS 140 Complete Parameter List” starting on page 39.
The following table lists the basic parameters.
S = Parameters can be modified only when the drive is stopped.
Code Name
User S
Group 99
START-UP DATA
9902
APPLIC MACRO
Selects application macro.Sets parameter values to their default
values. Refer to “Application Macros” starting on page 29, for detailed
description of each macro.
0 = FACTORY MACRO
4 = MOTOR POT
1 = ABB STANDARD
5 = HAND - AUTO
2 = 3-WIRE
6 = PID CONTROL
3 = ALTERNATE
7 = PREMAGN
á
Default value: 0 (FACTORY MACRO )
9905
MOTOR NOM VOLT
Nominal motor voltage from motor rating plate. Range of this
parameter depends on the type of the ACS 140 (200/400 V unit).
Selection for 200 V units:
200, 208, 220, 230, 240 V
á
Selection for 400V units:
380, 400, 415, 440, 460, 480 V
Default value for 200 V unit: 230 V
Default value for 400 V unit: 400 V
9906
MOTOR NOM CURR
Nominal motor current from motor rating plate. Values for this
parameter range from 0.5* I N - 1.5* IN, where IN is nominal current of
the ACS 140.
Default value: IN
9907
MOTOR NOM FREQ
Nominal motor frequency from motor rating plate.
á
á
Range: 0 - 300 Hz
Default: 50 Hz
9908
MOTOR NOM SPEED
Nominal motor speed from motor rating plate.
á
Range 0 - 3600 rpm.
Default: 1440
The table continues on the next page.