Download Modicon M340 for Ethernet

Transcript
TCP/IP Technical Characteristics
Modbus
Communications
This service enables communications through the Modbus protocol between a
Modicon M340 PLC and:
z a Quantum PLC
z a Premium PLC
z a PC with supervisor software
z another device complying with the Modbus protocol
The following figure shows the Modbus communications over open TCP/IP
connections:
1
2
3
4
5
6
Modicon M340 PLC (1)
Modicon M340 PLC (2)
Modbus protocol
Quantum server/client
client supervisor
TCP/IP Ethernet
The same module can communicate with a remote device in client mode (for
example a Quantum PLC) and another remote device in server mode (for example
a supervisor PC).
In the above figure, Modicon M340 PLC (1) is the client to the Quantum PLC. It
opens the TCP/IP connection and sends Modbus messages to the Quantum.
Modicon M340 PLC (2) is the server to the supervisor. The supervisor has opened
a TCP/IP connection for sending Modbus messages to Modicon M340 PLC (2).
31007131 03 07/2008
331