Download User Manual

Transcript
Agency
Markings
Operating
Temperature
CE, CB
0°C to 40°C (32°F to 104°F) in Online mode, with linear
derating for altitude
NOTE Thermal protection switches load to Bypass in case of
overheating.
-20°C to 40°C (-4°F to 104°F) with batteries
Storage
Temperature
-25°C to 55°C (-13°F to 131°F) without batteries
Transit
Temperature
Relative
Humidity
Operating
Altitude
-25°C to 55°C (-13°F to 131°F)
0–90% noncondensing
Up to 3,000 meters (9,843 ft) above sea level
Transit Altitude
Up to 10,000 meters (32,808 ft) above sea level
Audible Noise
<55 dBA at 1 meter typical
Leakage
Current
<1.5 mA
Table 20. Battery Runtimes (in Minutes) at 100% Load (ALL Models)
Model
Internal Batteries
+ 1 EBP
+ 2 EBPs
+ 3 EBPs
+ 4 EBPs
1K
5
22
41
65
87
2K
5
23
44
71
100
69