ANNUNCIATOR Alarm Annunciator Communication ANC8/ANC16 has one isolated RS485 port. As software protocol MODBUS RTU is implemented in the device. Supported functions of MODBUS RTU are as follows: • Read Holding Registers (03H) • Write Single Register (06H) • Write Multiple Registers (10H) RS485 Connect Line / Diagram Modbus Table Address 0 1 2 3 4 5 6 7 8 9 10 11 50 51 52 53 54 55 56 57 Parameter Details Alarm lags for channels Status of channels’ dip-switch Status of config. dip-switch Latest log index Seconds Minutes Hours Day Month Year Baud Rate Slave ID R/W RO RO RO RO R/W R/W R/W R/W R/W R/W R/W R/W Data Type 16 bit word 16 bit word 16 bit word 16 bit word 16 bit word 16 bit word 16 bit word 16 bit word 16 bit word 16 bit word 16 bit word 16 bit word Function 03H 03H 03H 03H 03H-06H-10H 03H-06H-10H 03H-06H-10H 03H-06H-10H 03H-06H-10H 03H-06H-10H 03H-06H-10H 03H-06H-10H Log 1 Day and month Log 1 Year and hours Log 1 Minutes and seconds Log 1 Data Log 2 Day and month Log 2 Year and hours Log 2 Minutes and seconds Log 2 Data RO RO RO RO RO RO RO RO 16 bit word 16 bit word 16 bit word 16 bit word 16 bit word 16 bit word 16 bit word 16 bit word 03H 03H 03H 03H 03H 03H 03H 03H 13