3.1 Variable Area (Setting Range) List
Variable
Address
type
Parameter name
Setting (monitor) value
0036
PV Change Color
H'00000000 (0): Orange
H'00000001 (1): Red
H'00000002 (2): Green
H'00000003 (3): Red to green: When ALM1 is ON
H'00000004 (4): Green to red: When ALM1 is ON
H'00000005 (5): Red to green to red: Within PV stable band: Green
Outside stable band: Red
H'00000006 (6): Green to orange to red: Within PV stable band: Orange
Outside stable band: Green, red
H'00000007 (7): Orange to green to red: Within PV stable band: Green
Outside stable band: Orange, red
C3 (83)
0037
PV Stable Band
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.01 to 99.99)
C3 (83)
0038
Alarm 1 ON Delay
H'00000000 to H'000003E7 (0 to 999)
C3 (83)
0039
Alarm 2 ON Delay
H'00000000 to H'000003E7 (0 to 999)
C3 (83)
003A
Alarm 3 ON Delay (See note 1.)
H'00000000 to H'000003E7 (0 to 999)
C3 (83)
003B
Alarm 1 OFF Delay
H'00000000 to H'000003E7 (0 to 999)
C3 (83)
003C
Alarm 2 OFF Delay
H'00000000 to H'000003E7 (0 to 999)
C3 (83)
003D
Alarm 3 OFF Delay (See note 1.)
H'00000000 to H'000003E7 (0 to 999)
C3 (83)
003E
Transfer Output Type
H'00000000 (0): OFF
H'00000001 (1): Set point
H'00000002 (2): Set point during SP ramp
H'00000003 (3): PV
H'00000004 (4): MV monitor (heating)
H'00000005 (5): MV monitor (cooling)
H'00000006 (6): Valve opening
C3 (83)
003F
Transfer Output Upper Limit
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFB1E1 to H'00007E90 (−19999 to 32400) (See note 2.)
C3 (83)
0040
Transfer Output Lower Limit
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFB1E1 to H'00007E90 (−19999 to 32400) (See note 2.)
C3 (83)
0041
Linear Current Output
H'00000000 (0): 4 to 20 mA
H'00000001 (1): 0 to 20 mA
C3 (83)
0042
Input Shift Type
H'00000000 (0): Temperature input 1-point shift
H'00000001 (1): Temperature input 2-point shift
C3 (83)
0043
MV at Stop and Error Addition
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83)
0044
Auto/Manual Select Addition
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83)
0045
RT
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83)
0046
HS Alarm Use
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83)
0047
HS Alarm Latch
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83)
0048
HS Alarm Hysteresis
H'00000001 to H'000001F4 (0.1 to 50.0)
C3 (83)
0049
LBA Detection Time (See note 3.)
H'00000000 to H'0000270F (0 to 9999)
C3 (83)
004A
LBA Level
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.01 to 99.99)
C3 (83)
004B
LBA Band
Temperature: H'00000000 to H'00007E90 (0.0 to 3240.0)
Analog: H'00000000 to H'0000270F (0.00 to 99.99)
Note 1:
Note 2:
Note 3:
Advanced
function
setting
Initial setting
Advanced
function
setting
Not displayed on the Controller display when Alarm 3 is not assigned to the output.
The setting (monitor) range depends on the transfer output type setting. (See the setting data list for details.)
This parameter can be set only for ON/OFF control.
3-9
Com Data for
CompoWay/F
C3 (83)
Level