SECTION 5 Modbus Communications Procedure 5.1 Data Format The data format complies with the Modbus (RTU) communications protocol, so commands from the host and responses from the E5CN/ AN/EN-H are contained in data blocks called frames. The structure of the command and response frames is described below. In the following explanations, hexadecimal values are expressed by adding the prefix H’ before the number, e.g., H’02. Numbers and alphabetic characters without the H’ prefix are ASCII characters. ■ Command Frame When using RTU mode, start with a silent interval of at least 3.5 character times and end with a silent interval of at least 3.5 character times. Slave Function address code 1 Data CRC-16 1 2 bytes CRC-16 calculation range Modbus Silent interval of 3.5 character times minimum. Slave address Specify the unit number. The unit number can be set between H’00 to H’63 hexadecimal (0 to 99 decimal). Specify H’00 for a broadcast transmission. No responses will be returned for broadcast transmissions. Function code The function code is a 1-byte hexadecimal code that indicates the type of command sent from the host device. Data This is the text data associated with the specified function code. Specify the required data, such as the variable address or setting data. (Set in hexadecimal.) CRC-16 Cyclical Redundancy Check This check code is calculated with the data from the slave address to the end of the data. The check code is 2-byte hexadecimal. Silent interval of 3.5 character times minimum. 5-2