parameters
i
vacon
Code
Parameter
Min
Max
P4.13
Accel2 Frequency
Threshold
0.00
P3.2
Hz
0,00
527 0,00 = disabled
P4.14
Decel2 Frequency
Threshold
0,00
P3.2
Hz
0,00
528 0,00 = disabled
P4.15
External Brake:
Open Delay
0,00
320,00
s
0,20
Delay to open brake
1544 after Open frequency
limit is reached
P4.16
External Brake:
Open Frequency
limit
0,00
P3.2
Hz
1,50
Opening frequency from
1535 forward and reverse
direction.
P4.17
External Brake :
Close Frequency
limit
0,00
P3.2
Hz
1,00
Close frequency from
1539 positive direction if no
run command active.
P4.18
External Brake :
Close Frequency
limit in Reverse
0,00
P3.2
Hz
1,50
Close frequency from
1540 negative direction if no
run command active.
P4.19
External Brake :
Open/Close Current limit
0,0
200,0
Unit Default
%
20,0
ID
• 79
Note
The brake is not opened
if the current does not
exceed this value, and is
closed immediately if
1585 current goes below.
This parameter is set as
a percent of Motor nominal current.
Table 8.5: Ramps and brakes setup