#HAPTER
CGCM Unit Software Interface
)NPUT$ATA4ABLESCHEDULEDREAD
The Input data table contains time-critical status data read from the CGCM unit
by the ControlLogix controller.
Data in this Controller Tag is automatically read by the host controller from the
unit at the scheduled update rate whenever a connection between the two exists.
This occurs independently of the user program. The Input data table can also be
read by using unscheduled messaging.
$ATA4YPE
The Input data table is automatically created by using module-defined data type
AB:1407_CGCM:I:0.
!SSEMBLY/BJECT)NSTANCE)NPUT$ATA4ABLE3CHEDULED2EAD
The Get Attributes Single service for instance 1 of the Assembly Object can
access the following information.
4ABLE'ET!TTRIBUTES3INGLE3ERVICE#ODEX%
.AME
!TTRIBUTE)$
$ATA4YPE
6ALUE
Data
3
UINT
See Scheduled Read Data
Table
Size
4
UINT
76
#ONFIGURATION#HECKING
No range checking is performed on the Input data table.
4ABLE3CHEDULED2EAD$ATA4ABLE
"YTE
3IZEIN
"YTES
4YPE
"ITS
4AG.AME
$ESCRIPTION
0
4
DINT
0…7
Status_32_bit
Connect Status
4
1
Bool
0
RevVARFlt
Reverse kVAR Fault
Bool
1
RevPwrFlt
Reverse kW Fault
Bool
2
OvrExcFlt
Over-excitation Fault
Bool
3
Ovr_I_Flt
Over-current Fault
Bool
4
Undr_V_Flt
Under-voltage Fault
Bool
5
Ovr_V_Flt
Over-voltage Fault
Bool
6
UndrFreqFlt
Under-frequency Fault
Bool
7
OvrFreqFlt
Over-frequency Fault
Rockwell Automation Publication 1407-UM001H-EN-P - November 2014
5NITS
2ANGE
-
0=Inactive,
1=Active