PROPORTIONAL mode with 0-10Vdc reference signal:
This kind of functioning allows steam production proportionally to reference signal 0-10V.
Example: a 6V reference signal will lead humidifier to produce 60% of steam referring to
software variable Pr. So if Pr= 70% will be 42%. To set the second level variable S9=2 and
make a bridge between terminal block 11 and 12, connect 0-10V reference signal to terminals
13 and 14, +V to terminal 13, GND to terminal 14.
Segnale esterno di
riferimento 0‐10V
Enabling
External 0‐10 V
reference signal
Steam production request
-
PROPORTIONAL mode with 4-20mA humidity probe:
This kind of functioning allows steam production in proportional mode, humidifier will regulate
automatically the production of steam as per ambient request. Enabling is provided by a 420mA humidity probe that regulates steam production, also allowing visualization of ambient
relative humidity, directly on humidifier display. To set the second level variable S9=1 and
make a bridge between terminal block 10 and 11, connect 4-20mA humidity probe signal to
terminals 8 and 9, signal RH to terminal 9, +V to terminal 8.
RH% Amb. humidity
transducer
-
Enabling
RH% Amb. humidity
transducer (4‐20mA)
Steam production request
The proportional band Bp is the percentage value of humidity near to the set point, inside this
value the humidifier works in proportional mode. Example: if the proportional band is set on
default value 10% (-5% / +5% set point value) and the humidity is set to 50%, under 45% the
humidifier will works to 100% of steam production; over 55% of humidity the humidifier will
not produce steam. Between 45% and 55% the humidifier will adjust the steam production
optimally.