Download Reference Manual Adjustable Frequency AC Drive
Transcript
2-28 Detailed Drive Operation [DigIn 3 Sel] can be set to the following values: Value 0 1 2 3 4 5 6 7 8 Description “Not Used” “Normal Stop” “Start” “Run” “Clear Faults” “Stop-CF” “Jog 1” “Jog 2” “Fwd/Reverse” Value 9 10 11 12 13 23 24 25 Description “CurLim Stop” “Coast Stop” “Aux Fault” “AuxFault Inv” “User Select” “Logix Motion” “+Hrd OvrTrvl” “-Hrd OvrTrvl” [DigIn x Debounce] sets a delay time to allow any bounce in the digital input to settle out. This parameter has a range of 0 to 15.5 milliseconds. When [DigIn x Sel] is set to “User Select,” the function of the digital input is determined by the following: • [DigIn x Data] determines any bits that should be permanently set. [DigIn x Data] sets the value of [DigIn x User Data] except for the bit chose in [DigIn x Bit] • [DigIn x Data] determines the bit you wish to toggle based on whether the digital input is on or off • [DigIn x User Data] will have the same bits that are set in [DigIn x Data]. Then the bit that was chosen in [Digin x Bit] will toggle based on whether the digital input is on or off. A designation (sink) parameter is then linked to [DigIn x User Data] so that it determines the value of that sink parameter Configuration Example DigIn 1 will be setup to determine the value of [Speed Ref Sel]. DigIn 1 will toggle [Speed Ref Sel] between a value of 1 “Speed Ref 1” and 5 “Speed Ref 5.” • [DigIn 1 Sel] = “User Select” • [DigIn 1 Data] = 0000 0000 0000 0000 0000 0000 0000 0001 • [DigIn 1 Bit] = 2. This means when we toggle Digital Input 1, bit 2 of [DigIn 1 User Data] will toggle. When Digital Input 1 is off [DigIn 1 User Data] will be equal to [DigIn 1 Data]. In other words, [DigIn 1 User Data] will equal 0000 0000 0000 0000 0000 0000 0000 0001 (a value of 1). When Digital Input 1 is on [DigIn 1 User Data] will be equal to [DigIn 1 Data] plus whatever bit was set in [DigIn 1 Bit]. In other words [DigIn 1 User Data] will equal 0000 0000 0000 0000 0000 0000 0000 0101 (a value of 5). [Speed Ref Sel] is linked to [DigIn 1 User Data]. Now [Speed Ref Sel] will toggle between a value of 1 and 5.