• When choosing the type: Integral, one must set following groups of parameters: - Unit and events - Numeric settings - Time settings - Alarm settings In the window of parameters ,, Totalizer units and events” following parameters are programmed: Unit: select defined units or program the own unit. Record to the log: after selecting the “Enabled” option set the frequency of the totalizer (integral) data saving to the Statistic log (see section 7.11) Totalizer disabled by: select the logic channel which the logic state 1 (ON) disables the totalizer action ( the state in the disabling moment will be preserved). Totalizer reset by: select the logic channel in which the change of the logic state from 0 (OFF) to 1 (ON) will cause the setting of the totalizer state on its value minimally programmed (see numeric settings) and the count restart. In the window of parameters ,, Totalizer numeric settings” following parameters are programmed: Decimal point: Edition of the parameter 0…4 Count direction:Addition/Subtraction Min./Max value: edition of the parameter ± 1000000000 Threshold: edition of the parameter 0…10000 Multiply by: edition of the parameter 0…1000000000 Min./Max. value: edition of the parameter ± 1000000000 85