Download VAMPSET manual
Transcript
5.4 Making Protocol Settings 5 Setting Groups VAMPSET IEC-103 slave number setting range 1…254 (255 is reserved for broadcasts) this is used as link layer address and as common address of ASDU in application layer IEC-103 bit rate 9600 or 19200 bps Meas sending interval This setting is used for restricting the sending measurements. The next measurement is not sent until the time interval has elapsed since last sending. During this time the device responses to class 2 poll by „data not available‟ message. ASDU 6 response time mode This setting defines which time stamp is sent in response to a time synchronising message. The following modes are available: SYNC Device sends back the same time stamp that the master sent in the synchronising message. SYNC + PROC Device adds its internal processing time to the time stamp in the synchronising message and sends the sum in the response message. MSG Device sends back its internal time stamp of the first received bit of the synchronising message from master. This mode can be very useful because subtracting the time stamp found in the response message from the time stamp that the master sent in the sync message gives the time difference between the master and the device just before the new sync became valid. MSG + PROC Otherwise the same as MSG but internal processing time is added to the time stamp Data configuration Data configuration is divided into Digital and Analog sections. Any line can be changed or removed and new lines can be added to both sections. 50 VVAMPSET/EN M/B006