Bypass Options (continued)
Automatic Bypass 1, 2, 3
(Option BA)
This option provides a means to manually or automatically (upon a drive fault) switch a single motor
from drive control to bypass (across the line) operation. Separate Bulletin 100 (where available)
contactors are provided for drive output and bypass operation, and are electrically interlocked. A
Bulletin 193 Class 10 overload is also provided for motor protection while operating in the bypass
mode – refer to Motor Thermal Overload Data in the Selection Guide section. Door-mounted
“Drive/Off/Bypass” and “Auto Bypass Off/On” selector switches are provided. Optional “Bypass Mode”
and “Auto Bypass Enable On” pilot lights are available (option D42).
Manual Bypass with SMC Plus 1, 2, 3
(Option BS)
This option provides a means to manually switch a single motor from drive control to bypass
(across the line) operation. An SMC Plus™ solid state controller provides soft start capability when first
switching to bypass operation. Separate Bulletin 100 (where available) contactors are provided for drive
output, SMC output and total bypass. All contactors are electrically interlocked. A door-mounted
“Drive/Off/Bypass” selector switch is provided. Optional “Drive Mode” and “Bypass Mode” pilot lights
are available (option D41).
Automatic Bypass with SMC Plus 1, 2, 3
(Option BD)
This option provides a means to manually or automatically (upon a drive fault) switch a single motor
from drive control to bypass (across the line) operation. An SMC Plus solid state controller provides
soft start capability when first switching to bypass operation. Separate Bulletin 100 (where available)
contactors are provided for drive output, SMC output and total bypass. All contactors are electrically
interlocked. Door-mounted “Drive/Off/Bypass” and “Auto Bypass Off/On” selector switches are
provided. Optional “Bypass Mode” and “Auto Bypass Enable On” pilot lights are available (option D42).
Manual Bypass with SMC Plus /
Pump Option 1, 2, 3
(Option BP)
This option provides a means to manually switch a single motor from drive control to bypass
(across the line) operation. An SMC Plus (with the pump control option) solid state controller provides
soft start and smooth acceleration capability when first switching to bypass operation and smooth
deceleration when stopping in bypass. Separate Bulletin 100 (where available) contactors are provided
for drive output, SMC output and total bypass. All contactors are electrically interlocked. A doormounted “Drive/Off/Bypass” selector switch is provided. Optional “Drive Mode” and “Bypass Mode”
pilot lights are available (option D41).
Automatic Bypass with SMC Plus/
Pump Option 1, 2, 3
(Option BC)
This option provides a means to manually or automatically (upon a drive fault) switch a single motor
from drive control to bypass (across the line) operation. An SMC Plus (with the pump control option)
solid state controller provides soft start and smooth acceleration capability when first switching to
bypass operation and smooth deceleration when stopping in bypass. Separate Bulletin 100 (where
available) contactors are provided for drive output, SMC output and total bypass. All contactors are
electrically interlocked. Door-mounted “Drive/Off/Bypass” and “Auto Bypass Off/On” selector switches
are provided. Optional “Bypass Mode” and “Auto Bypass Enable On” pilot lights are available
(option D42).
Bypass Mode Circuit Breaker
(Option CC)
This option is for disconnecting power only, and is not intended for branch circuit protection.
Branch circuit protection is provided by the bypass fusing option -FM. Most ratings will utilize a motor
circuit protector (MCP) type breaker. Where MCP’s are not available a circuit breaker will be provided.
All switches include handle operators, door interlocking and are padlockable.
Bypass Mode Non-Fused Disconnect Switch
(Option DT)
This option is for disconnecting power only, and is not intended for branch circuit protection. Branch
circuit protection is provided by the bypass fusing option -FM. An Allen-Bradley Bulletin 194R rotary
switch is provided on A-C frame drives. A flange mount or rotary style switch (1494 F where possible) is
provided on D frame drives and larger. All disconnect switches are non-fusible, door interlocked and
padlockable.
Bypass Mode Motor Fuse Block
(Option FM)
This option provides a fuse block only. Fuses must be customer supplied and installed.
This option is used in conjunction with any bypass option for motor branch circuit protection.
1 The Bypass Operation capability provided by this option is not intended for maintenance of the drive or entry into the enclosure with power applied while
operating in the bypass mode. Maintenance Bypass (positive lockout) is available as a custom option.
2 Bypass Options do not include the required 120V AC control power. Control power may be supplied remotely by the user, or as part of the drive package by
ordering a Control Power option CF, CP or CT – see Options section.
3 SMC style bypass options will include short circuit fusing for the SMC. Once the motor is up to speed it is transferred from the SMC control to total across-the-line
operation, which required option FM to have branch circuit protection.
75