Download LANCOM Outdoor Wireless Guide
Transcript
LANCOM Outdoor Wireless Guide 쮿 Chapter 3: Lightning and surge protection Scenario 3: EN The access point is not installed inside the building but outdoors, for example directly next to the antenna, in order to reduce the length of cable between the antenna and the access point. Safety clearance >100 cm Potential-equalization line (PEL) (PEL) 16mm² Cu 230 V LAN PoE - 48 V Surge-protection adapter LANCOM SA-LAN SA-LAN OUTDOOR ACCESS POINT SA-5L Surge-protection adapter LANCOM SA-5L In this case, the AirLancer Extender SA-5L surge-protection adapter is installed directly between Access Point and antenna and grounded for example via the antenna's potential equalization line. If any LANCOM OAP model is operated with the supplied rod antenna instead of with an external antenna, the lightning protection adapter AirLancer Extender SA-5L cannot be employed due to the connector shape. In this case it is imperative that a lightning rod is employed! 쮿 If the Access Point is installed outside, its grounding and that of the AirLancer Extender SA-5L are connected with the antenna's conductor, for example via the clamps on the antenna's mounting. 40