Download User Manual XUSL2E-XUSL4E Original
Transcript
Safe Mounting Distance Detection Zone Approaches Normal (Perpendicular) Approach This figure displays the normal (perpendicular) approach to the detection zone: S: 1: 2: 3: 4: Minimum safe distance Hazardous zone Detection zone Direction of approach Fixed guard If the operator’s direction of approach is perpendicular to the detection zone as shown in the figure and the resolution of the system is 40 mm or less, use the following formula to calculate the safe mounting distance, S: S= (K x T) + C S = (2000 mm/s x T) + 8 x (R – 14 mm), where: K = 2000 mm/s T = Total response time C = 8 x (R – 14 mm), but not less than 0 R = Resolution of the light curtain in millimeters. You can calculate the safe mounting distance S, using this formula with values for T and R that are appropriate for the light curtains. The following lists the conditions for safe mounting distance calculation: If the calculated value of S is greater than or equal to 100 mm (3.94 in.) and less than or equal to 500 mm (19.68 in.), use the calculated value for the safe mounting distance. If the calculated value of S is less than 100 mm, use 100 mm as the safe mounting distance. If the calculated value of S is greater than 500 mm (19.68 in.), recalculate S with an alternate value for K as shown in the given formula: S = (1600 mm/s x T) + 8 x (R – 14 mm) EAV6589801 05/2015 41