Download Manual - InduProgress
Transcript
Chapter 5 Troubleshooting|VFD-M-D Series 5.10 Motor Speed cannot be Changed Motor can run but cannot change speed Modify the setting Check if the setting of the max. frequency is too low Yes Yes No If the setting of Pr.05-17toPr.05-31 Yes is too high Check to see if frequency is Yes out of range (upper/lower) boundaries No Yes If finished with executing Pr.05-15 No Yes Is it in PLC mode Press UP/DOWN key Yes to see if speed has any change No No Yes If there is any change of the signal that sets Yes frequency (0-10V and 4-20mA) If the setting of Pr.05-00 to Pr.05-14 are the same No Modify the setting Check if the wiring between M1~M6 to DCM is correct Yes Check if frequency for each step is different No No No Check if the wiring of external terminal is correct Correct wiring No Yes Change defective potentiometer Yes Change frequencysetting No Check if accel./decel. time is set correctly Yes Please set suitable accel./decel. time by load inertia Maybe AC motor drive has malfunction or misoperation due to noise. Please contact DELTA. Revision May 2009, MDE5, SW V1.1 5-7