Download User Manual - Klockner Moeller Parts

Transcript
06/03 AWB2528-1480GB
Wiring with MFD-Titan
Function of the GET function block
1
2
Figure 102:Signal diagram of GET function block
1: GT..Q1
2: value on GT..QV>
Seven-day time switch
MFD-Titan is equipped with a real-time clock which you can
use in the circuit diagram as a 7-day time switch and a year
time switch.
h
The procedure for setting the time is described under
Section “Setting date, time and daylight saving time” on
Page 305.
MFD provides 32 seven-day time switches HW01 to HW32
for a total of 128 switching times.
Each time switch has four channels which you can use to set
four on and off times. The channels are set via the parameter
display.
The time is backed up in the event of a power failure and
continues to run, although the time switch relays will no
longer switch. The contacts are kept open when deenergized. Refer to Section “Technical data”, Page 345 for
information on the buffer time.
Wiring of a 7-day time switch
A 7-day time switch is integrated into the circuit diagram as
a contact.
216
For Immediate Delivery call KMParts.com at (866) 595-9616