1-82 Process Control Instructions (ALM, D2SD, D3SD, DEDT, FGEN, LDLG, PIDE, POSP, RMPS, SCL, SRTP, TOT) Arithmetic Status Flags: Arithmetic status flags are set for the PositionPercent output. Fault Conditions: none Execution: Condition: Function Block Action: Structured Text Action: prescan OpenOut and CloseOut are cleared. OpenTime = 0 CloseTime = 0. OpenOut and CloseOut are cleared. OpenTime = 0 CloseTime = 0. instruction first scan The internal cycle timer is reset. The internal cycle timer is reset. The instruction calculates OpenTime and Close Time. The instruction calculates OpenTime and Close Time. instruction first run No action taken. No action taken. EnableIn is cleared EnableOut is cleared, the instruction does nothing, and the outputs are not updated. na EnableIn is set The instruction executes. EnableOut is set. EnableIn is always set. The instruction executes. postscan No action taken. No action taken. Example: In this example, the POSP instruction opens or closes a motor-operated valve based on the CVEU output of the PIDE instruction. The actual valve position is wired into the Position input and optional limit switches, which show if the valve is fully opened or closed, are wired into the OpenedFB and ClosedFB inputs. The OpenOut and CloseOut outputs are wired to the open and close contacts on the motor-operated valve. Structured Text FlowController.PV := WaterFlowRate; PIDE(FlowController); FlowValve.SP := FlowController.CVEU; FlowValve.Position := FlowValvePosition; FlowValve.OpenedFB := FlowValveOpened; FlowValve.ClosedFB := FlowValveClosed; POSP(FlowValve); OpenFlowValveContact := FlowValve.OpenOut; CloseFlowValveContact := FlowValve.CloseOut; Publication 1756-RM006D-EN-P - May 2005