Download IT. S811 Soft Starter
Transcript
IT. S811 Soft Starter User Manual November 2006 0x804A (32842) Auto Reset Enable Size: 1 byte Default: 0 (Disabled) Description: Enables the auto fault reset function. An auto reset will be performed after the thermal memory has cooled below 75% and all other fault conditions have been corrected. This parameter is displayed as Reset Mode in the DIM 0x804B (32843) Start Method Size: 1 byte Default: 0 Description: Unsigned integer which sets the S811’s starting method: 0x00 – Voltage Ramp Start 0x01 – Current Limit Start 0x02 – Reserved 0x03 – Pump Start (option) 0x04 – Reserved 0x804E (32846) Motor Communication Loss Action Size: 1 byte Default: 0x00 Description: Determines motor action in the event of a communications timeout in network communications. This parameter only applies when the node is on line and in Auto mode. The following values are allowed: 0x00 = Auto Stop – go to auto and stop 0x01 = Auto Run1 – go to auto and Run1 1 0x02 = Auto Run2 – go to auto and Run2 1 0x03 = Hold Last – hold last state 0x04 = Local Stop – go to local and stop 0x05 = Local Run1 –go to local and Run1 1 0x06 = Local Run2 – go to local and Run2 1 0x07 = All Stop (fault)– leave in last control mode (local or auto) and stop 2 Note 1: Warning, these actions may cause the S811 to start once network communications are restored. Note 2: All Stop causes a fault and needs a reset to clear. 0x804F (32847) Motor Rated Volts (volts) Size: 2 bytes Default: 480 volts Description: Unsigned integer set to match the incoming line voltage. This setting calibrates the Over Voltage and Under Voltage Faults 0x806C (32876) Firmware Version List Size: 4 bytes Default: N/A Description: Unsigned integer identifies firmware versions of all firmware components of the S811. Consists of 2 2-byte elements. 0x806D (32877) Hardware Version List Size: 2 bytes Default: N/A Description: Hardware version of all components of the system MN03902002E For more information visit: www.EatonElectrical.com I-11