FX3U/FX3UC Series PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM) FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details 5.4.10 BFM #29: Error status Initial value: H0000 Numeric data type: Hexadecimal (H) Error data is assigned each bit of BFM #29. 1. Assignment to each bit of BFM #29 Bit No. Item Description b0 Error detection If one of b1 to b11 is turned on, b0 will turn on. b1 O/G error Gain setting error: error in offset gain data or in EEPROM offset gain setting b2 Power supply error 24 V power is not supplied properly. Check the wiring condition or the supplied voltage. b3 Hardware error FX3U-4DA may be defective. Please contact the nearest Mitsubishi Electric distributor office. b4 - - b5 Error setting function for output setting upon PLC stop The setting value of the function for output setting upon PLC stop (BFM #5) is not set correctly. Correctly set the value. b6 Upper/lower limit function setting error The setting value of the upper/lower limit function (BFM #41 to BFM #48) is not set correctly. Correctly reset the value. b7 Error in corrective function The setting value of the corrective function by load resistance setting by load resistance (BFM #51 to #54) is not set correctly. (Valid only in voltage output Correctly set the value. mode) b8 Table output function setting error The setting value of the table output function is not set correctly. Correctly set the value. b9 Status automatic transfer setting error The setting value of the status automatic transfer function (BFM #61 to #63) is not set correctly. Correctly set the value. b10 Over-scale The analog output is out of the specified range. b11 Disconnection detection Wire-break has occurred. (The details are indicated by BFM #28.) (Valid only in current output * The bit is turned on when BFM #28 is not 0.) mode) b12 Setting data change prohibited b13 to b15 Setting change is prohibited. - - 2. Caution regarding error status If the error cause is eliminated, the error bit will turn off. 3. Error status data automatic transfer function (b0 of BFM #60) If the error status with automatic transfer to data register is specified in BFM #61, the data in BFM #29 can be transferred to a specified data register. Only when an error is detected, data will be automatically transferred from FX3U-4DA to the PLC. For this reason, the PLC does not need the program for reading data, and the scan time of the PLC can be shortened. → For a detailed description of the status automatic transfer function, refer to Subsection 5.4.18. D-28