10.4
Calibrating Range with SFC,
Continued
Procedure, continued
Figure 52
Typical Calibration Hookup.
ST 3000
+ Red
+
TEST
- SIGNAL +
+
-
24Vdc
Power
Supply
250 Ω
- Black
Low
Pressure
Head
DVM
(See NOTES)
Dead Weight
Tester
(See NOTES)
SFC
NOTES: The digital voltmeter must have a 0.02% accuracy or better.
The calibration-standard input source must have a 0.02% accuracy.
The 250 ohm resistor must have a 0.01% tolerance or better.
7/00
ST 3000 Release 300 and SFC Model STS103 User’s Manual