AS 60-200KVA
Electrical connections
General
Connections for the APOSTAR are provided by terminal strips located in the lower third of
the cubicle. The cables can be brought up to the cubicle from all four sides and led in
through the bottom of the cubicle. A false floor in the installation room is not necessary.
The tables and drawings hereafter indicate the cable connection points and the cable
dimensions according to DIN VDE 0298.
IMPORTANT
You must ensure that the phases of the a.c. connections (clockwise
rotating field) and the polarity of the battery connections are correct, as
incorrect connections can cause damage to the equipment.
Terminal assignment and cable sizes
NOTE
1. The battery cables should not be longer than 15 m; the voltage drop
not more than 1.5 %. Please consult us if you are unable to meet these
requirements. Page 20 shows the recommended cable types. When
determining the cable lengths bear in mind that about 0.50 m of cable is
required inside the cubicle.
2. In the event of a fault in the UPS set, e.g. short-circuit, the input fuse of
the unit must trip before the mains fuse since only then is transfer to the
bypass mode possible without a break. Diazed/l.v.h.r.c. type GL fuses
should therefore be used as mains fuses. The minimum fuse rating can
be obtained from the table hereafter.
UPS-power (kVA)
AS IV_Tech_Data.doc 09.04.02
Fuse (A)
Mains 1
Mains 2
60
125
100
80
160
125
120
200
200
160
250
250
200
315
315