Download AS 60-200KVA TECHNICAL DATA
Transcript
AS 60-200KVA Type AS UPS rated output kVA (cos ϕ = 0,8) Distortion factor (EN 50091-1) – linear load – non linear load Crestfactor Overload – 3ph – 1ph Short-circuit characteristics – 3ph – 1ph Inverter efficiency with rated load Automatic Bypass Rated voltage Rated frequency Overload capacity – 10 min – 100 ms Inverter/Bypass changeover time – inverter fault – overload or man. operation Bypass/Inverter changeover time Required fuse protection Diazed/NH Type GL A General Data Overall efficiency – 100% load % – 75% load % – 50% load % – 25% load % Power dissipation – 100% load kW – 75% load kW – 50% load kW – 25% load kW 3 Air rate required m /h Noise level at a distance of 1m Permiss. ambient temperature Relative humidity Installation altitude Humidity class Protection type Insulation group Radio interference level Dimensions – width – depth – height Weight Floor loading AS IV_Tech_Data.doc 09.04.02 kg 2 kg/m 60 60 80 80 120 120 160 160 200 200 < 1% < 5% ≥3 150 % 30 s, 125 % 10 min 220 % 30 s, 180 % 10 min 200 % 20 ms, 150 % 3 s 350 % 20 ms, 260 % 3 s 98 % 400 V 50 Hz 150 % 1000 % 100 125 2 ms 0 ms 0 ms 200 91 92 92 92 92 4,75 5,6 8,5 10,3 13 2000 2000 ca. 900 804 895 1400 ca. 900 250 315 2500 2500 2500 67 dB(A) 0 – 40°C daily average ≤ 35°C 5 % - 95 % without condensation <1000 m above mean sea level without power reduction DIN/IEC 721 2-1-09/86 IP 21 (DIN/VDE 0470 part 11/92 IEC 529) DIN/VDE 0110, Overvoltage category 2, Fouling factor 2 EN 50091-2 Standard class A We reserve the right to change without notice! ca. 1100 see section 0 993 815 1802 ca. 850 ca. 850 2