Download USER MANUAL SCROLL CHILLER
Transcript
1 GENERAL DESCRIPTION OF THE APPLICATION The software application to which this manual relates has been designed to manage all Cooling Only, Heat Pump and Freecooling Chillers equipped with scroll compressors. For this purpose we have implemented the option of using either a pCOXS or pCO1 electronic controller, based on the type of chiller. Given the differences in the inputs/outputs, some logics refer only to the more complete control system. 2 CONTROL LOGIC 2.1 CONTROL OF INLET TEMPERATURE Inputs used: • Evaporator inlet water temperature Parameters used: • Control setpoint (Setpoint menu) • Proportional band for inlet temperature control (User menu → Setpoints and parameters → H9). • Type of control (User menu → Setpoints and parameters → H3) • Integration time (if Proportional + Integral control is enabled) (User menu → Setpoints and parameters → H3) • Hysteresis percentage for single compressor (User menu → Setpoints and parameters → H3) Outputs used: • Compressors On/Off EX: Diagram showing control logic with 4 compressors and 100% hysteresis: 4 = 4 compressors ON . . 1 = 1 compressor ON 0 = 4 compress. OFF 4 ∆ = Differential / no. of compressors 2 Hysteresis 3 1 0 SetP SetP+ ∆ SetP+2∆ SetP+ Diff inlet water T Figure 1: Control with 4 compressors – 100% hysteresis EX: Diagram showing control logic with 4 compressors and 70% hysteresis: 4 = 4 compressors ON . . 1 = 1 compressor ON 0 = 4 compress. OFF 4 ∆ Differential / no. of compressors 2 Ist. 3 1 0 SetP SetP+ ∆ SetP+2∆ SetP+ Diff inlet water T Figure 2: Control with 4 compressors – 70% hysteresis sw.Chiller-Scroll 1.01 7 Scroll Manual 1.14