Transcript
Revision 3.8 WebRelayTM Users Manual can operate the gate from another room using a web browser. Another option (not shown here), is to connect another pushbutton switch to the input of a second WebRelay TM device in a room across the building. The second device could be configured to send control messages to the first device each time the new pushbutton is pressed. As a result, there is a second pushbutton that could operate the gate. 2.2.4 Optically-Isolated Input Connection The optically-isolated inputs can be used to control the internal relays, control remote relays (over the network), or simply to monitor the state of a discrete device. To use these inputs, connect a DC control voltage directly to the input and ground, and set up the function of the input using the configuration pages. A current limiting resistor is provided internally, so no external resistors are required as long as the maximum input voltage is not exceeded. If an AC signal, or a signal greater than the rated input voltage needs to be detected by the WebRelay™, use a signal conditioner to convert the signal to a DC signal within the input range. Connecting "dry contacts" to the optically-isolated inputs: A dry contact switch can be connected to the input of the WebRelay™. One side of the contact is connected to +5V OUT, the other side is connected to Input+, and a jumper cable connects the V IN- to the INPUT-. When the contact is closed, it applies 5V to the input terminals. Xytronix Research & Design, Inc. page 20