Numerics Examples: Editing an Array of Numeric Values 89 The following examples show different ways of displaying numeric values on a screen and allowing an operator to change them. Example 3: Set Bit Cursor Points (for keypad terminals) Numeric Keypad Enable Button I:011/0–17 — Keypad Numeric Input (RIO) N7:11 — Keypad Numeric Input (DH+/ControlNet) I:010/1 — Enter Key Control (RIO) N7:10/1 — Enter Key Control (DH+/ControlNet) Set Bit Cursor Point I:010/0 – Control (RIO) N7:10/0 – Control (DH+/ControlNet) Numeric Data Display O:010/0–17 – Displayed Value (RIO) N7:12 – Displayed Value (DH+/ControlNet) " Note: Although the above illustration shows both Remote I/O, and DH+ or ControlNet addresses, an application can have only one type of address. The illustration is intended as an example only, for all types of applications. The operator enters numeric values via the Numeric Keypad that appears when the Numeric Keypad Enable Button is pressed. Numeric Data Displays display values in the PLC. Set Bit Cursor Point objects are placed next to each Numeric Data Display to provide a means of selecting which value to change. The following PLC-5/15 rungs show how the data can be read into the PLC and transferred to the corresponding Numeric Data Display. Rung for Remote I/O Application I:010 ] [ 0 Enter Bit I:010 ] [ 1 MOV MOVE SOURCE: DEST: I:011 O:010 20383 Publication 2711E-6.15 – November 1998