Download FB Library Start-up Guide
Transcript
2-13 Temperature Control Unit CJ1W-TC001/101/003/103/002/102/004/104 2-1-4. Temperature Control Function Setting In this example, only SW8 is set to ON to use factory default setting as it is. Switch function and factory settings ON at right SW No. Function ON OFF 1 Operation when CPU unit is in PROGRAM mode Continue Stop 2 Temperature units (°C/°F) °F °C 3 Data format 16-bit binary 4-digit BCD 4 Control operation (loops 1 and 3) Forward (cooling) Reverse (heating) 5 Control operation (loops 2 and 4) Forward (cooling) Reverse (heating) 6 Control method ON/OFF control PID control 7 Initialize settings in EEPROM Initialize Do not initialize 8 Transfer settings in EEPROM Transfer Do not transfer Factory setting OFF ON 2-1-5. Wiring of thermocouple Connect the wiring based on the following terminal assignment. To use Loop 1, connect the thermocouple to Input 1 and the control target output to Output 1. * Do not connect any cable to the N.C terminal 2-1-6. Power On Turn the PC main unit on. Hardware setting described in the chapter 1 must be done when the power is turned off. After power on, SW settings are read (SW settings are read only at power on) . 2-1-7. Creating I/O Table Connect CX-Programmer (Online) when creating I/O table.