• The generator set Specification Sheet indicates the maximum fuel inlet and return restrictions, the maximum fuel flow and the fuel consumption. Table 12 indicates minimum hose and pipe sizes for connections to a supply tank or day tank that is relatively close to the set and at approximately the same elevation. Hose and pipe size should be based on the maximum fuel flow rather than on the fuel consumption. (The maximum fuel flow is approximately twice the full-load fuel consumption on GeneratorJoe generator sets rated 200/175 kW and larger.) It is highly recommended that the fuel Inlet and return restrictions be checked before the set is placed in service. TABLE 12. MINIMUM FUEL SUPPLY HOSE AND PIPE SIZES FUEL SUPPLY LINE FUEL RETURN LINE 0-10 FEET (0-3 METRES) PIPE I.D. FLEX INCHES HOSE (MM) SIZE 10-50 FEET (3-15 METRES) FLEX PIPE I.D. HOSE INCHES SIZE (MM) 0-10 FEET (0-3 METRES) FLEX PIPE I.D. HOSE INCHES SIZE (MM) 10-50 FEET (3-15 METRES) FLEX PIPE I.D. HOSE INCHES SIZE (MM) 0-15 NO. 6 5/16 (7.9) NO. 6 13/32 (10.3) NO. 4 3/16 (4.8) NO. 6 5/16 (7.9) 15-20 NO. 8 13/32 (10.3) NO. 8 1/2 (12.7) NO. 4 3/16 (4.8) NO. 6 5/16 (7.9) 20-80 NO. 10 1/2 (12.7) NO. 10 5/8 (15.9) NO. 8 13/32 (10.3) NO. 10 1/2 (12.7) 80-100 NO. 12 5/8 (15.9) NO. 16 7/8 (22.3) NO. 8 13/32 (10.3) NO. 10 1/2 (12.7) 100-160 NO. 16 7/8 (22.3) NO. 16 7/8 (22.3) NO. 10 1/2 (12.7) NO. 12 5/8 (15.9) 160 > NO. 16 7/8 (22.3) NO. 16 7/8 (22.3) NO. 12 5/8 (15.9) NO. 12 5/8 (15.9) MAXIMUM GPH Based on four straight fittings, two 90º fittings and minimal fuel lift height. • Separate fuel return lines to the day tank or supply tank must be provided for each generator set in a multiple-set installation to prevent the return lines of idle sets from being pressurized. Also, a fuel return line must not include a shutoff device. Engine damage will occur if the engine is run when the line is shut off. • A day tank is required whenever pipe friction and/or supply tank elevation, either below the fuel pump inlet or above the fuel injectors, would cause an excessive fuel inlet or return restriction. Some generator set models are available with an integral skid- mounted or sub-base day tank. For critical start applications, where generator sets are paralleled or must satisfy emergency start-time requirements, it is recommended that a fuel tank or reservoir be located such that the lowest possible fuel level is not less than 6 inches (150mm) above the fuel pump inlet. This will prevent air from accumulating in the fuel line while the set is in standby, eliminating the period during startup when it has to be purged. 45