Download caution! - Climatemaster
Transcript
Residential Packaged Units - 60Hz Puron® R e v. : 4 J a n . , 2 0 1 2 Electrical - Low Voltage Wiring Thermostat Connections The thermostat should be wired directly to the CXM board (units with PSC fan). Units with optional ECM motor include factory wiring from the CXM board to the ECM interface board. Thermostat wiring for these units should be connected to the ECM interface board. Figure 18 shows wiring for 50YD/50YE units with PSC or optional ECM motor. See “Electrical – Thermostat” for specific terminal connections. Figure 18: GT-PX/GT-PG Low Voltage Field Wiring Low voltage field wiring for units with PSC FAN (ECM board will not be present) Low Water Temperature Cutout Selection The CXM control allows the field selection of low water (or water-antifreeze solution) temperature limit by clipping jumper JW3, which changes the sensing temperature associated with thermistor FP1. Note that the FP1 thermistor is located on the refrigerant line between the coaxial heat exchanger and expansion device (TXV). Therefore, FP1 is sensing refrigerant temperature, not water temperature, which is a better indication of how water flow rate/temperature is affecting the refrigeration circuit. The factory setting for FP1 is for systems using water (30°F [-1.1°C] refrigerant temperature). In low water temperature (extended range) applications with antifreeze (most ground loops), jumper JW3 should be clipped as shown in Figure 19 to change the setting to 10°F [-12.2°C] refrigerant temperature, a more suitable temperature when using an antifreeze solution. All residential units include water/ refrigerant circuit insulation to prevent internal condensation, which is required when operating with entering water temperatures below 59°F [15°C]. Figure 19: FP1 Limit Setting Low voltage field wiring for units with ECM fan CXM PCB JW3-FP1 jumper should be clipped for low temperature operation 21