SETTING/OPERATING INSTRUCTIONS (Continued) RC2163FE
IMPORTANT SAFETY INSTRUCTIONS
When installing and operating this Product and other associated equipment, basic safety precautions should always be followed,
including the following:
1. Read and follow all instructions.
2. This Control must be installed by a qualified electrician, according to National and Local Electrical Codes.
3. Install this control not less than 5 feet (3 meters in Canada) from inside edge of pool and 1 foot (30 cm) above ground. USE
COPPER CONDUCTORS ONLY, rated Min. 70˚C.
4. Do not exceed the maximum ratings of individual components, wiring devices, and current carrying capacity of conductors.
5. For Control grounding, bonding, installing and the wiring of underwater lights, refer to Article 680 of the National Electrical Code or Article
68 of the Canadian Electrical Code.
6. The Control should not operate any equipment which would cause bodily injury or property damage should it be activated
unexpectedly.
READ, FOLLOW AND SAVE THIS INSTRUCTION MANUAL
INSTALLATION RC2163FE
This Control can operate either a 120 volt or 240 volt, single speed pump, together with a gas heater and up to three
24 volt valve actuators. It has a 120 volt and 24 volt connection for a remote installed switching device and also has
a connection for a freeze or heater protection device to turn ON the pump if needed.
IMPORTANT: High and low voltage conductors should not occupy the same conduits or compartments.
1. Follow wiring diagram on Page 4 and prepare your
Make sure the installation is securely grounded and
installation layout. Make sure only copper (solid or
bonded if required.
stranded), 70˚C minimum rated conductors are used,
properly sized and suitable for the installation. Each
5. Remove screw next to Heater Switch and gain
piece of equipment must be grounded properly.
access to printed circuit (P.C.) board assembly in
IMPORTANT: Neutral must always be connected
low voltage compartment. Follow wiring diagram on
to the white lead of the control.
page 4, plug valve actuators into designated sockets
on P.C. board and make heater connections to ter2. Hang Control on a flat vertical surface or other
minals 1, 2 and 3.
support, using hardware suitable for the purpose. 3.Prepare the necessary conduit runs, including one
for the remote - located 120 volt switching device
(switch, timer or radio receiver), underwater light(s),*
terminate them at both ends and pull-in the
conductors as specified by the installation layout.
*If this control is to be used for direct connection
to under-water lights, a Nonmetallic Hub Kit
should be used. Order 156PA13713A for a 1/2”
Kit, 156PA13714A for a 3/4” Kit or 156PA13715A
for a 1” Kit.
Place jumper between terminals L and H if heater
is single stage. See page 4 for details. Replace
P.C. board assembly.
6. If selected, install remote - located low voltage control
(Switch, or Timer). See wiring on page 4.
7. Check wiring, tightness of connections and
grounding.
Close wiring compartment and test installation.
8. Set timer, see instructions below.
4. Follow wiring diagram on page 4, make LINE and
LOAD (Pump) connections in the high voltage
compartment.
To Review Program: Press TIMER key repeatedly.
When done, press CLOCK key to return to the time
of day.
To Operate Equipment in Spa Mode:
1.Activate control.
2.After using the spa, make sure that control is
back in the POOL mode.
To Cancel/Change Part of the Program: Press Timer
key repeatedly until the particular ON or OFF time
appears. Set new ON or OFF time.
To Operate Heater:
Heater Selector Switch is provided to save on heating
cost during the summer months or prevent over-heating of pool water if heater is the single thermostat type.
Set switch to POOL AND SPA mode if the heater is the
DUAL thermostat type and set thermostats on heater
to the desired pool and spa water temperatures.
Set switch to SPA ONLY mode if the heater is the
SINGLE thermostat type or only the spa water needs
to be heated. Set switch to OFF if no heater operation
is needed.
To Override the Automatic Operation one time:
Press OVR. key to turn ON/OFF equipment.
NOTE: Timer will resume automatic operation with the
next opposite setpoint.
To Suspend Automatic Operation Permanently:
Press SELECT key to move indicator bar to the desired
ON or OFF position. Note: Timer will not resume automatic operation until indicator bar is repositioned above
the word AUTO.
TROUBLESHOOTING
Symptom
Possible Cause(s)
Corrective Action
Control will not operate
in SPA mode
Defective remote control
Defective relay
Blown fuse
Replace remote control Replace relay
Replace fuse
Timer is not turning
pump ON/OFF for
daily filtration
Defective timer
Defective relay
Timer is set to ON/OFF
No program in memory
Dead battery
Replace timer
Replace relay
Set timer to AUTO
Set program - see instructions
Replace battery
Valve actuators(s) is/are
not working
Frozen valve
Defective actuator
Loose connection
Blown fuse
Check/Lubricate valve
Replace actuator
Check connections
Replace fuse
Pump inoperative
Open circuit breaker
Defective relay
Defective pump
Check power supply
Change relay
Check pump
ENCLOSURE DETAILS
SETTING / OPERATING INSTRUCTIONS
Programming Instructions
To Set or Change the Time of Day: To clear entire
memory, press key. Hold down the CLOCK key
while pressing either the HOUR or MINUTE keys.
Continue pressing until the desired number is shown.
Then simply lift finger off the CLOCK key to set.
To Set Program (ON/OFF times): Press TIMER key
once to enter into program mode. Display will show
“1 ON-- --”. Press the HOUR key and then the
MINUTE key to select the desired first ON time. Press
TIMER key once. Display will show “1 OFF -- --”.
Repeat previous step to select the desired first OFF
time. Repeat the entire sequence to complete up to
eight total ON/OFF times as desired. When programming is done, press the CLOCK key then the SELECT
key repeatedly until the indicator bar is above the word
“AUTO”.
Display
Reset port
to cancel all
prior settings
2
158AS11682 2
Indicator LED “ON”
when connected to
power source and
contacts are closed
ON/AUTO/OFF
Select Key
Function Keys