Service
Removing the control board
Remove the grille
Remove the cover of the control box
Remove the following connectors from the
board by unlocking the clip on the connector:
CN510: Louver motor – 20 wires
CN34 : Float switch – 3 wires
CN504: Drain pump – 2 wires
CN101: TC sensor – 2 wires
CN102: TCJ sensor – 2 wires
CN104: Room temperature sensor – 2 wires
CN333: Fan motor power supply – 5 wires
CN334: Fan motor position detection – 3 wires
Unlock the 6 board clips (edge spacer) and
remove the board
Installing the control board
Reverse the above steps
Back to main menu