Download 2 - Toshiba

Transcript
Check code
Check code name
[P29] / [16]
Compressor position
detective circuit error
(TCC-L / AI-NET)
Are the connectors and wiring
to the compressor normal?
NO
Cause of operation
1. Wire connection error.
2. Compressor error
3. IPDU P.C. board error
Check and correct circuit and
wires, i.e. to the compressor, etc.
Check code
Check code name
[–] / [97]
AI-NET communication line error
Cause of operation
AI-NET communication line error
(TCC-L / AI-NET)
Are AI-NET X and Y
communication lines normal?
NO
Correct communication line.
YES
YES
YES
Is it grounded?
Compressor error ® Replace
NO
Is there a winding short?
(Is winding resistance 0.6 to 1.2 W?)
YES
Compressor error ® Replace
Are connections of CN01,
CN02, and CN03 connectors
on network adaptor P.C. board
(MCC-1401) and CN309
and CN41 connectors on
indoor P.C. board normal?
YES
Is the winding open circuit?
Compressor error ® Replace
NO
NO
Check connection of A, B terminal.
Correct communication line of remote controller.
YES
Is there no connection error
on the power line?
Check IPDU P.C. board.
Failure ® Replace
Correct connection of connectors.
YES
Are remote controller
communication lines
(A, B) normal?
NO
NO
YES
Correct power line.
NO
143
Is not main power supply
turned on?
YES
Turn on the main power supply.
NO
Did a block-out occur?
YES
Clear check code.
NO
Check code
Check code name
[P31] / [47]
Other indoor error
(Group follower unit error)
(TCC-L / AI-NET)
Cause of operation
Other indoor unit in the group has a error.
Is the network
address changed by the main
remote controller?
YES
NO
When the header unit of the group detects [E03, L03, L07, L08 error], the follower unit(s) in the group display [P31]
error and stop. There are no check code displays or alarm record on the main remote controller.
YES
Eliminate noise, etc.
Is there any noise etc.?
NO
Can other indoor units
be controlled from AI-NET
central remote controller,
or is the operation status
of indoor unit the same?
Unavailable (Others are same.)
®
Check central controller.
Failure
Replace
YES
Does the network adaptor
P.C. board LED (D01) turn on?
NO
Can the
NO
indoor unit be
controlled from the main
remote controller?
®
Check indoor P.C. board.
Failure
Replace
YES
YES
Check power transformer of the
network adaptor P.C. board (MCC-1401).
Failure
Replace
®