Check code Check code name [P29] / [16] Compressor position detective circuit error (TCC-L / AI-NET) Are the connectors and wiring to the compressor normal? NO Cause of operation 1. Wire connection error. 2. Compressor error 3. IPDU P.C. board error Check and correct circuit and wires, i.e. to the compressor, etc. Check code Check code name [–] / [97] AI-NET communication line error Cause of operation AI-NET communication line error (TCC-L / AI-NET) Are AI-NET X and Y communication lines normal? NO Correct communication line. YES YES YES Is it grounded? Compressor error ® Replace NO Is there a winding short? (Is winding resistance 0.6 to 1.2 W?) YES Compressor error ® Replace Are connections of CN01, CN02, and CN03 connectors on network adaptor P.C. board (MCC-1401) and CN309 and CN41 connectors on indoor P.C. board normal? YES Is the winding open circuit? Compressor error ® Replace NO NO Check connection of A, B terminal. Correct communication line of remote controller. YES Is there no connection error on the power line? Check IPDU P.C. board. Failure ® Replace Correct connection of connectors. YES Are remote controller communication lines (A, B) normal? NO NO YES Correct power line. NO 143 Is not main power supply turned on? YES Turn on the main power supply. NO Did a block-out occur? YES Clear check code. NO Check code Check code name [P31] / [47] Other indoor error (Group follower unit error) (TCC-L / AI-NET) Cause of operation Other indoor unit in the group has a error. Is the network address changed by the main remote controller? YES NO When the header unit of the group detects [E03, L03, L07, L08 error], the follower unit(s) in the group display [P31] error and stop. There are no check code displays or alarm record on the main remote controller. YES Eliminate noise, etc. Is there any noise etc.? NO Can other indoor units be controlled from AI-NET central remote controller, or is the operation status of indoor unit the same? Unavailable (Others are same.) ® Check central controller. Failure Replace YES Does the network adaptor P.C. board LED (D01) turn on? NO Can the NO indoor unit be controlled from the main remote controller? ® Check indoor P.C. board. Failure Replace YES YES Check power transformer of the network adaptor P.C. board (MCC-1401). Failure Replace ®