website http://www.lgservice.com e-mail http://www.lgeservice.com/techsup.html LG LG Multi Type Air Conditioner SERVICE MANUAL MODEL: L2-H242GL0 L2-C242GL0 CAUTION • BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL. • ONLY FOR AUTHORIZED SERVICE PERSONNEL. Multi Air Conditioner Service Manual TABLE OF CONTENTS Safety Precautions......................................................................................................................................3 Product Specifications ......................................................................................................................................7 Dimensions ..........................................................................................................................................................9 Refrigeration Cycle Diagram .............................................................................................................................11 Wiring Diagram ...................................................................................................................................................12 Electronic Control Device..................................................................................................................................13 Schematic Diagram ...........................................................................................................................................15 Functions ............................................................................................................................................................18 Operation Details................................................................................................................................................21 2-way, 3-way Valve..............................................................................................................................................28 Cycle Troubleshooting Guide............................................................................................................................32 Electronic Parts Troubleshooting Guide ..........................................................................................................33 Installation ..........................................................................................................................................................41 Operation ............................................................................................................................................................53 Disassembly of the parts (Indoor unit).............................................................................................................55 Exploded View and Replacement Parts List ....................................................................................................58 2 Multi Air Conditioner Safety Precautions Safety Precautions To prevent injury to the user or other people and property damage, the following instructions must be followed. ■ Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications. WARNING This symbol indicates the possibility of death or serious injury. CAUTION This symbol indicates the possibility of injury or damage. ■ Meanings of symbol used in this manual are as shown below. Be sure not to do. Be sure to follow the instruction. WARNING ■ Installation Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit. • There is risk of fire or electric shock. Install the panel and the cover of control box securely. • There is risk of fire or electric shock. Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open. • Moisture may condense and wet or damage furniture. Always install a dedicated circuit and breaker. • Improper wiring or installation may cause fire or electric shock Always ground the product. • There is risk of fire or electric shock. Use the correctly rated breaker or fuse. • There is risk of fire or electric shock. Service Manual 3 Safety Precautions Do not modify or extend the power cable. • There is risk of fire or electric shock. For installation, always contact the dealer or an Authorized Service Center. • There is risk of fire, electric shock, explosion, or injury. Do not install, remove, or reinstall the unit by yourself (customer). • There is risk of fire, electric shock, explosion, or injury. Do not install the product on a defective installation stand. • It may cause injury, accident, or damage to the product. Be cautious when unpacking and installing the product. • Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator. Be sure the installation area does not deteriorate with age. • If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury. ■ Operational Do not touch(operate) the product with wet hands. • There is risk of fire or electrical shock. 4 Multi Air Conditioner Do not place a heater or other appliances near the power cable. Do not allow water to run into electric parts. • There is risk of fire and electric shock. • It may cause There is risk of fire, failure of the product, or electric shock. Safety Precautions Do not store or use flammable gas or combustibles near the product. • There is risk of fire or failure of product. If strange sounds, or smell or smoke comes from product. Turn the breaker off or disconnect the power supply cable. • There is risk of electric shock or fire. Gasolin Do not open the inlet grille of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.) Be cautious that water could not enter the product. • There is risk of physical injury, electric shock, or product failure. • There is risk of fire, electric shock, or product damage. Service Manual 5 Safety Precautions CAUTION ■ Installation check for gas (refrigerant) leakage after installation or repair of product. • Low refrigerant levels may cause failure of product. Install the drain hose to ensure that water is drained away properly. • A bad connection may cause water leakage. Keep level even when installing the product. • To avoid vibration or water leakage. 90˚ ■ Operational Use two or more people to lift and transport the product. • Avoid personal injury. Use a soft cloth to clean. Do not use harsh detergents, solvents, etc. Do not touch the metal parts of the product when removing the air filter. They are very sharp! • There is risk of fire, electric shock, or • There is risk of personal injury. damage to the plastic parts of the product. x Wa Thinner Do not step on or put anyting on the product. (outdoor units) • There is risk of personal injury and failure of product. 6 Multi Air Conditioner Do not insert hands or other objects through the air inlet or outlet while the product is operated. • There are sharp and moving parts that could cause personal injury. Product Specifications Product Specifications 1. L2-C242GL0 Operation Item A + B unit A or B unit Unit Cooling Capacity Btu/h(kcal/h) 12,000(3,517) 24,000(7,034) Moisture Removal l/h 1.4 1.4 x 2 Power Source ø, V, Hz Air Circulation m3/min Noise Level(Hi/Med/Low) dB(A) 1Ø, 220, 60HZ Indoor 8.5 Outdoor 42 Indoor 39/35/31 Outdoor 54 Input W 1,250 2,350 Runnig Current A 5.8 10.8 Btu/h.w 9.6 10.21 E.E.R. Motor Output Dimensions(W x H x D) Net. Weight Refrigerant(R-22) W mm kg Indoor 10.0 Outdoor 90 Indoor 900 x 285 x 156 Outdoor 870 x 655 x 320 Indoor 8 Outdoor 61 g A: 750, B: 750 (at 7.5m) Airflow Direction Control(Up & Down) O Remocon Type Service Valve Drain Hose L.C.D Wireless Liquid 1/4"(6.35) Gas 1/2"(12.7) O Plasma Filter Optional Connecting Cable 1.5mm2 Power Cord 2.5mm2 Service Manual 7 Product Specifications 2. L2-H242GL0 (Cooling/Heating) Operation Item A + B unit A or B unit Unit Cooling Capacity Btu/h(kcal/h) 12,000(3,517) 24,000(7,034) Moisture Removal l/h 1.4 1.4 x 2 Power Source ø, V, Hz Air Circulation m3/min Noise Level(Low) dB(A) 1Ø, 220, 60HZ Indoor 8.5 Outdoor 42 Indoor 39/35/31 Outdoor 54 Input W 1,250/1,150 2,300/2,150 Runnig Current A 5.8/5.3 10.8/9.7 Btu/h.w 9.60 10.43 E.E.R. Motor Output Dimensions(W x H x D) Net. Weight Refrigerant(R-22) W mm kg Indoor 10.0 Outdoor 90 Indoor 900 x 285 x 156 Outdoor 870 x 800 x 320 Indoor 8 Outdoor 61 g A: 730, B: 730 (at 7.5m) Airflow Direction Control(Up & Down) O Remocon Type Service Valve Drain Hose L.C.D Wireless Liquid 1/4"(6.35) Gas 1/2"(12.7) O Plasma Filter Optional Connecting Cable 0.75mm2 Power Cord 2.5mm2 8 Multi Air Conditioner Dimensions Dimensions 1. Indoor Unit H D W Installation plate MODEL DIM L2-C242GL0, L2-H242GL0 W mm 900 H mm 285 D mm 156 Service Manual 9 Dimensions 2. Outdoor Unit L4 H L3 L1 L9 L10 L10L10 L2 D W L6 MODEL DIM L5 L7 L8 L2-C242GL0, L2-H242GL0 W mm 870 H mm 655 D mm 320 L1 mm 370 L2 mm 25 L3 mm 630 L4 mm 25 L5 mm 546 L6 mm 160 L7 mm 160 L8 mm 64 L9 mm 76.5 L10 mm 50 10 Multi Air Conditioner Gas side 3-Way valve Liquid side 2-Way valve Refrigeration Cycle Diagram Refrigeration Cycle Diagram 1. L2-C242GL0 Indoor Unit Outdoor Unit LIQUID SIDE CAPILLARY TUBE 2-WAY VALVE HEAT EXCHANGER (EVAPORATOR) A-UNIT HEAT EXCHANGER (CONDENSER) B-UNIT COMPRESSOR B GAS SIDE 3-WAY VALVE COMPRESSOR A 2. L2-H242GL0 Indoor Unit Outdoor Unit COMPRESSOR-A COOLING HEATING DEICE 4-WAY VALVE 3-WAY VALVE HEAT EXCHANGER COMPRESSOR-B 4-WAY VALVE HEAT EXCHANGER A-UNIT B-UNIT CAPILLARY TUBE 2-WAY VALVE Gas Liquid Max. piping length (m) 1/2" 1/4" 15 Pipe Size (Diameter : inch) CAPILLARY TUBE Max. piping elevation (m) 8 ex) Capillary Cooling & Deice Service Manual 11 Wiring Diagram Wiring Diagram Indoor Unit 1. L2-C242GL0 2. L2-H242GL0 BR CN-TH THERMISTOR CN-U/D CN-AC/DC TRIAC OR MOTOR DC PWB ASM CN-AC/DC AC PWB ASM BK STEP MOTOR CN-MOTOR YL CN-TAB1 SH-CAPA BR 3 2(N) 1(L) TO OUTDOOR UNIT 4 RD AIR H.V. ASM BK CLEAN (PLASMA) BK SAFETY S/W1 BK FUSE 250V T2A 3 RY-COMP BK BK SAFETY S/W2 CN-DISP OPTION GN/YL SW(FORCE) DISPLAY PWB ASM T/BLOCK INDOOR WIRING DIAGRAM 3854A20135F 3854A20142F Outdoor Unit CAPACITOR R S BR O.L.P C COMP "B" BL C YL H S WH T/B 3 RD R BK COMP "A" F BK 2. L2-H242GL0 CAPACITOR 1. L2-C242GL0 OR OR C GN/YL O.L.P BR BK T/B 2 RD BK RD BL 3 NO 6 RD 1 BL 7 NC C POWER RELAY 8 BL BK GN/YL BK WH YL OR T/B 4 T/B 1 MOTOR BK BK WH 1(L) 2(N) 3 A-UNIT 3 2(N) 1(L) B-UNIT 1(L) 2(N) TERMINAL BLOCK MAIN POWER TO INDOOR UNIT OUTDOOR WIRING DIAGRAM 12 Multi Air Conditioner 3854A20216C 3854A20135E Electronic Control Device Electronic Control Device Indoor Unit 1. MAIN P.C.B ASSEMBLY(L2-C242GL0) 2. MAIN P.C.B ASSEMBLY (L2-H242GL0) ROOM PIPE RESET +5V J15 GND GND J6 +5V +5V GND +5V J14 6870A90097A 6871A20266 J13 Service Manual 13 Electronic Control Device Outdoor Unit • MAIN P.C.B ASSEMBLY(L2-H242GL0) Display P.C.B Assembly 14 Multi Air Conditioner Schematic Diagram Schematic Diagram Indoor Unit 1. L2-C242GL0 DC PART 2 AC PART 2 STEPPING MOTOR (UP/DOWN) DISPLAY Operation 1 BL PK YL OR RD S/W(FORCE) R01G~R04G LED1 220 5 CN-U/D 5 1 2 3 4 3 4 2 6 7 8 CN-DISP1 1 8 7 6 5V C02L 220uF SD 10V + 1 2 3 3 1 2 3 12V 7 8 IC01G KID65004AF HVB OUT R11H~R14H 20K 2012 C07D 103 50V 12V 5V R11H R12H R13H R14H INDOOR FAN 1 2 3 5 LED2 220 4 LED3 220 5 Sleep 5 Timer 4 LED4 220 4 Outdoor 3 3 1 2 3 1 1 2 2 3 6 3 2 9 1 5V 2 receiver 1 1 1 2 O IC04D S78DL05L 1W I 7805 Option GND RECEIVER 2 1 CN-CONT 2 CN-12V C08D 103 50V CN-HVB Vout Vcc HVB 5V + C09D 220 10V SD 3 A1 A2 1 G 2 COMP 7 6 9 7 6 5 4 3 2 1 8 IC01M KID65004AF OJ4H 5V 20K R02F 5V 1 8 5V 6 4 5V 1 2 3 11 4 5 6 7 8 9 10 12 13 14 15 16 L2 100uH 2 7 Option 2 3 3 4 4 5 5 1 1 BL PK YL OR RD STEPPING MOTOR (LEFT/RIGHT) 2 2 3 4 5 6 CN-L/R 7 8 16 15 14 13 12 11 10 9 1 A V s s B Z COMP 5 4 5V INT 6 3 SMPS C02D 104 7 2 12V R02E,20 R22H R23H R24H R25H R26H R01T 1K C03T 102 5V Q03T C104S Q02T A104S 5V Q01C KTC3198-Y 2SC5343 3 2 3.6V 1 Q01T C104S R07D 12K 5V C02T 102 D01T 1N4148 5V C01T 104 R02L,1K C01L 680pF/50V INT 5V R02H 12.1K 1% CN-TEL receiver CN-TH R05D 300K 1/4W 3216 D05D 1N4007 D08D LL4148 DC HIGH VOLTAGE GND 3 1 R04D 27k 1/8W 2012 5V R04H 6.2K 1% R06D 56K R01L 5.1K 5V Q04T A104S 4 6 IC01A KIA7036P S7136 R05H 10K 5V OSC01B CSTS0800MG03-T2 CRTL8.00MSOT C01A 0.01 50V R02A,20K 5V INT DC LOW VOLTAGE GND IC03D TLP181(V4 BL) NTC SCK-102 C01D 4.7uF 450V/SD R21H INDOOR FAN + INDOOR FAN R21H~R26H 12.1K, 1% R01B 1M 5V 5V BZ01E PKM13EPY-4002 R01E 1K 8 1 SD01D STO2D-200 IC01D TNY266P DC HIGH VOLTAGE GND S 2 BP 1 EN 4 D 5 OR6H OR5H OR4H OR3H OR2H OR1H Low O/L Hi Med F2 F1 33 36 35 34 38 37 42 41 40 39 44 43 47 46 45 48 IC02M KID65004AF AVref AVdd RESET X2 X1 Vss1 INT0 INT1 64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 A V d d 1 NEC UPD780023AGC-C Vdd0 Vss0 5V 5 INT D07D UG2D C04D 470/35V/SD + RY-COMP + C02C 220uF 10V/SD 3 6 4 17 18 1920 21 22 23 24 25 26 27 28 29 30 31. 32 12V DC HIGH VOLTAGE GND C05D 472M IC02D TLP181(V4 BL) R03D 39 1/8W 2012 12V 20K R02P 2012 3 1 OJ3H 20K R01P 2012 OJ2H 12V HVB OUT SCL WP Vcc 8 5 A0 SDA EEPROM CAT24WC01J 4 OJ1H CN-ACDC 12V L1 ZBF503D CN-ACDC C06D 330 25V SD R02D 20K ZD02D BZX55C11 DC LOW VOLTAGE GND 3 3 2 3 4 2 4 1 1 3 2 2 1 1 BD01D DF08M R06D 300K 1/4W 3216 ROOM-TH PIPE-TH C03J METAL FILM 100nF/275V/436D 3.9V, 1/2W 2.7 1/2W R19H 2.7 1/2W R18H C05H A104S 5V Q04T A104S RY-HOOK ZD05H TX C02T 0.001uF 50V R12H + - 4 8 5V 7 0.1uF/50V C02H 6.2K/1W 6 5 RX 1N4004 D01H~D04H 750 R14H 270 + 1.5KE56A ZD01H T1 R02H 6.2K 1/4W 7.5K T2 3 Q02M 1uF 63V PC01H R06H 3 4 TLP621BL 27 5V D01M 5V R07H 2K 51K 2 3 C04H 1uF 16V RA3 MCLR T0CLK VSS RB0 RB1 RB2 RB3 IC-DTMF HT9170B DV EST RI RA0 OSC1 18 17 16 15 14 1M R01B 12 Q1 13 Q0 10 Q3 11 Q2 Q2 DSO 0.1uF 50V C02X RB4 RB5 RB6 RB7 VDD OSC2 5V 15 Q3 DE Q0 Q1 14 10 11 12 13 100K R01X 16 17 (ST9170) VN 18 VDD GS VP VREF X1 D3 D2 D1 D0 5V TX RX OSC01B 0.01uF 50V C01X CST-4.00MGW AC220~240V 50/60Hz SH-CAPACITOR COMPRESSOR FAN MOTOR OUTDOOR INDOOR FAN MOTOR OE RA1 MICOM 2 3 RA2 PIC16C54CR 10K 1 OP1 OP2 10K 4 5 7 6 8 1 3 4 7 VSS NC NC X2 N L 1(L) 2(N) 9 6 5 8 9 DE 5V 1 2 DSO R17H R08H 100K RST DE BD R01M Q01M C3198Y R16H 100K OSC02B CST-3.58M 4.7K 1N4004 5V 3 2 2 2 1 1 1 1 1 CN-TAB1 T-BLOCK CN-MOTOR KIA7036P IC01A C09H 2 1 KTC2016 4.7K R04H Q03M 2 27 R05H 2222A + 1 3.6V 3 RY-COMP G4A-1A-E-LG 4 TRAICS SM1L43 R03J 680 1/2W 100 R03A 4.7K R02A 5.1V, 1/2W 4 5 TR01J ZNR02J TVR10561 T1 FUSE 250V/T2A ZNR01J TVR10561 TRANS R03H C03H 22uF 50V 0.1uF 50V ZD02H 50V 10uF C01A + 1K R01A ZD02H~ZD03H ZD03H C11H R13H RST 3 2 1 IC01J TLP762JF C08H 0.15uF 63V R02J 100,1/2W R04J 560 1/4W 3216 LM358 OP-AMP 1K R01H 1uF DC250V C01H OPTION 5V 0.1uF/50V C06H HR93F,5V G6A-234P,5V ZD04H BSP351L ZNR01 R15H 10K 1K 5V 1K R01T Q03T NF01J 15mH/1A C01J METAL FILM 100nM/275V/436D R01J 120, 1/2W INDOOR FAN 12V C104S Q01T R09H 0.01uF 100V 100uF/25V C01D BD 5V ZD04H~ZD05H TELE 2 1 + CN-PHONE CN-TELE 3 2 1 C104S Q02T C01T 0.001uF 50V D01T 1N4148 C02J METAL FILM 47nM/275V/435D Service Manual 15 NC STEP MOTOR LEFT/RIGHT BL PK YL OR RD BL PK YL OR RD ROOM-TH PIPE-TH STEP MOTOR UP/DOWN COM NO 2 3 3 3 4 3 4 5 4 5V 0.01 50V 5V 7805 I C07D 103 50V 12V DC LOW VOLTAGE GND 3 1 R03D 39 1/8W ZD02D BZX55C11 R02D 20K C06D 330 25V L1 ZBF503D Q01C KRC106S R01C,1K R02C,4.7K R01L,1K OP6 C01L 680pF 50V BZ01E R01E,1K R02E,20 R18H 10K 12.1K 10K 1% R16H R17H R02L,10K Q01M KRC106S M C02C 0.015 50V IC04D 7805 C08D 103 50V O 1 2 3 4 5 6 7 C01Z 0.01 50V R01Z,1K 8 IC01M KID65004AP 16 15 14 13 12 11 10 9 C02H 0.01 50V 1% C01H 1% 6.2K R04H AC PART R05C 4.7K C09D 220 10V + R02H 12.1K DC12V 10K R02Z REMOCON 5V INT D01M DC 12V CN-U/D CN-L/R 5 4 2 3 2 1 5 4 3 2 3 1 5 4 3 2 1 2 2 1 1 1 CN-TH 1 2 CN-SW 1 5V 5V OP4 D07D UG2D IC02D TLP181 C05D 472M 4 6 C04D 470/35V + C02D 104 SMPS IC01A S 2 BP 1 EN 4 D 5 5V 12V CN-ACDC DC12V 5V INT R03H,1K 2 2 1 IC01D TNY266P C01D 4.7uF 450V + 3 3 5 5 D6 R55/BUZ 15 6 6 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 7 7 VSS 8 8 XOUT XIN RESET’ R40/INT0 R41/INT1 R42/INT2 R43/INT3 R44/EC0 R45/EC2 R46/T10 R47/T30 R50/Sin R51/Sout R52/Sclk R53/Srdy 4 6 5V 3 1 R04D 27k 1/8W 2012 A16 R27 33 A15 R26 34 A14 R25 35 A13 R24 36 A12 R23 37 A11 R22 38 D08D 1N4148 R06D 300K 1/4W R05D 300K 1/4W BD01D DF08M Rx(Outdoor) Tx(Outdoor) FAN_MOTOR FAN_MOTOR Tx Rx D05D 1N4007 R20 40 R17 41 R16 42 R15 43 R14 44 R13 45 R12 46 R11 47 R10 48 R07 49 R06 50 R05 51 R04 52 R03 53 R02 54 A10 R21 39 A8 A7 A6 A5 A4 A3 A2 A1 A0 D7 D5 R54/WDTO D4 D3 R56/PWM0 R60/AN0 D2 D1 R62/AN2 R61/AN1 R00 56 D0 R63/AN3 R01 55 HALT R37 57 R57/PWM1 16 R34 60 R33 61 BRQ R36 58 14 13 12 C BRK R35 59 SYNC R64/AN4 R65/AN5 R66/AN6 R67/AN7 AVref NTC SCK-102 R01B,1M IC03D TLP181 4 4 CST-8.00MTW OSC01B C01A 0.01 50V R01A,1K 1 + RX TX AIR_CLEAN R01H,1K 11 10 9 8 7 6 5 4 R31 63 Wt R32 62 R30 64 RD 3 R/W MP 2 0.01 50V AVss Vdd 1 C01M SD01D STO2D-200 C02A 10uF/50V R03A,150 OP1 12.1K R11H R02A,4.7K OP2 12.1K R12H KIA7036P OP3 12.1K R13H C03D 680pF C01C 0.01 25V OP5 12.1K 12.1K 1% R14H R15H C01F,0.01/50V 4 3 2 1 C02F,0.01/50V C02J METAL FILM 47nM/275V TXD(Outdoor) RXD(Outdoor) DU VCC R01K 10K 560 DC 5V R02K,1K 6 ORG Vss 5 7 8 R04J Q01K KRC102S C01K 0.001 25V FAN_MOTOR 12V Q D C S AIR_CLEAN IC02M 4 3 1 2 T1 ZNR02J TNR561 T2 R03K 1K C02L D02K 1SR139-600 C04J 0.01uF,AC275V 100nF/275V C03J R01J 120,1/2W DC 5V DC 12V 220uF 16V DC 5V ZNR01J TVR10561 FUSE 250V/T2A R05K 15K,3W (82K,3W) ZNR01K 14D271 TRAICS SM1L43 D01K 1SR139-600 TR01J R03J 680, 1/2W DC 12V REMOCON DC 5V FAN_MOTOR R04G,220 R02G,220 R07G,220 R01G,220 R02F,10K C01J METAL FILM 100nM/275V IC02K(TLP627) (TLP127) 1 2 4 3 NF01J 15mH/1A R04K 680 4 5 9 10 11 12 13 14 15 16 R02T,10K IC01K(TLP621) (TLP181) R02J 100,1/2W 3 2 1 IC01J TLP762JF 8 7 6 5 4 3 2 1 KID65004AP R01T,10K LIMIT SWITCH EEPROM R04F,10K R03T,10K 5V R04T,10K R01F,1K R05T,10K 16 Multi Air Conditioner 2 1 2 1 5 6 7 5 6 7 9 8 7 6 5 4 3 2 CN-SUB 9 8 7 6 5 4 3 2 1 4 4 1 2 3 2 1 1 3 8 8 CN-DISP1 3 1 2 4 5 1 2 4 5 1 1 T-BLOCK 2 2 3 3 CN-Airclean 3 CN-MOTOR MICOM GMS81516 L N C 7 6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 7 6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 INDOOR FAN MOTOR 8 8 102 C01S 1K R01S Bit2 Bit0 10K R02S TACT S/W REMO HVB SH-CAPACITOR Option 3 2 1 10K R03S 3 2 C B D E 10K R06S 5 6 20 9 8 7 6 2 R04S F 0 1 4 8 1 A 7 4 8 5 4 3 4 5 6 Bit1 Bit3 10K R07S 10K R05S DC 12V DC 5V DC 12V DISPLAY_PCB Vcc Vout GND SUB_PCB DC 12V 3 2 1 3 2 1 CN-SUB 9 8 7 6 5 4 3 2 1 3 2 1 3 2 1 Telecontrol Schematic Diagram 2. L2-H242GL0 Schematic Diagram Outdoor Unit • L2-H242GL0 2 4 3 2 1 4 2 1 3 2 3 1 3 1 CN-TH1 B TH A TH C TH CN-TH2 DC 5V 12 11 9 4 5 6 8 R02H 6.2K 1% R04H 6.2K 1% C01H~C03H 0.01 25V IC02M(KID65004AP) 13 R06H 12.1K 1% R01H,1K R03H,1K 8 7 6 5 4 3 2 34 35 36 37 38 39 40 41 42 9 1 R05H,1K P77 3 P73 P74 P75 2 14 IC01M 15 8 P76 6 7 1 9 16 10 P72 11 P71 P70 5 P07 4 3 12 2 13 14 31 33 30 32 12 29 10 13 28 11 14 27 25 15 24 16 RESET 26 XOUT 17 22 23 18 (VASS)VSS XIN 19 20 21 MICOM TMP87C846 DC 5V 5V R01C C10D 103 10K C11D 0.01 25V DC 5V CAPA. 0.01 25V TEST S/W DC 5V R01M,R02M 10K VDD P22 P21 P20 P17 P16 P15 P14 P13 P11 P12 P10 P67 P66 P65 P64 P63 P62 P61 P60 VAREF L02D DC 12V RY-BP4 RY-4WAY(A) RY-4WAY(B) RY-SV4 RY-SV3 RY-SV2 RY-SV1 RY-BP2 RY-BP1 15 P05 RY-COMP(B) R01G,1.5K P04 P06 L1(SV1) P03 P02 R02G,1.5K 1 DC5V L2(SV2) P01 TEST P00 R04G,1.5K C01A 0.01 25V R01A,1K R05G,1.5K L3(SV3) 3 R03A,100 R02A,4.7K L4(SV4) 1 7036P C02A 10 50V R01B,1M L5(SV5) R03G,1.5K 16 RY-LOW (RY-SV5/HBP1) RY-HI + RY-COMP(A) DC 5V IC01A 2 OSC01B CST8.00MGW 100nH 5V G C08D 104 IC03D KID78L05BP O I 7805 C09D 220uF/50V C01K 0.001 25V Q01K KRC107M C02K 0.001 25V Q02K KRC107M C03K 0.001 25V Q03K KRC107M C04K 0.001 25V Q04K KRC107M C06K 0.001 25V Q05K KRC107M 39 R04D 3.3uH L01D 12V C04H-05H 0.01,25V C07D 330uF/35V R03D 150 ZD02D 11V DC 5V R01K,1K R05K,1K R09K,1K R13K,1K R17K,1K R02K 10K 3 4 2 1 4 3 IC01K(TLP621/421) 2 R04K 1K 1 3 1 2 IC02K(TLP627) 4 3 IC01K(TLP621/421) 4 3 1 2 IC04K(TLP627) 2 R08K 1K 1 4 IC01K(TLP621/421) 3 4 3 1 2 IC06K(TLP627) 2 R12K 1K 1 4 IC01K(TLP621/421) 3 4 3 1 2 IC08K(TLP627) 2 R16K 1K 1 4 IC09K(TLP621/421) 3 4 S 3,7,8 R03K 1.5K D01K 1SR139-600 R07K 1.5K D02K 1SR139-600 R11K 1.5K D03K 1SR139-600 R15K 1.5K D04K 1SR139-600 R19K 1.5K DC 5V D12K 1SR139-600 ST02D-170 (UF4005) DC310V OR1H XXX R07H 12.1K 1% IC10K(TLP627) 2 R20K 1K 1 R08H 12.1K 1% 3 1 OR2H XXX C03D 104 D D02D 5 EN 4 TNY IC01D 266P TNY266P 1 2 BP S/Trans OR3H XXX R01F 12.1K 1% R18K 10K R14K 10K R10K 10K R06K 10K C05D 681 6,7 4,5 D03D SB360 C06D (UF5402) 470uF/35V IC02D(TLP521) C04D 472/250VA C02J 100nF R01J D01D 1N4007 1M,1/2W 275V NTC01D 100D-9 C01D 15uF/ 450V R22K 82K,3W R21K 82K,3W D06K 1SR139-600 D05K 1SR139-600 D08K 1SR139-600 D07K 1SR139-600 D11K 1SR139-600 7 8 9 4 5 6 7 8 9 1 3 2 1 3 6 2 2 1 4 5 3 3 3 3 2 2 1 RY-4WAY3 2 1 RY-FAN OUT-A RY-4WAY4 1 RY-BP1 1 2 1 4 2 4 3 RY-SV1 2 3 3 1 3 2 1 RY-SV2 1 2 2 1 3 2 RY-SV3 RY-COMP(B) 2 CN-COM A ROOM B ROOM C ROOM D ROOM BYPASS1 BYPASS2 SV1 SV2 NEUTRAL LIVE COMP B COMP A CN-COMP SV4/4WAY2 SV3/4WAY1 CN-SV CN-BYPASS HBYPASS2 4WAY4 4WAY3 FAN1 CN-FAN D ROOM CN-POWER 3 1 C01J 100nF 275V RY-SV4 1 3 ZNR01J INR14D561K INR14D471K 1 RY-BP2 RY-FAN OUT-B (SV5) RY-BP4 RY-COMP(A) R24K 82K,3W R23K 82K,3W FUSE 250V/T3.15A R28K 82K,3W NF NF01J 15mH/1A 2 4 Service Manual 17 Functions Functions Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature • Room temperature sensor. (THERMISTOR) Room temperature control • Maintains the room temperature in accordance with the Setting Temp. Starting Current Control • Indoor fan is delayed for 5 seconds at the starting. Time Delay Safety Control • Restarting is inhibited for approx. 3 minutes. Indoor Fan Speed Control • High, Med, Low, Chaos Operation indication Lamps (LED) --- Lights up in operation --- Lights up in Sleep Mode --- Lights up in Timer Mode --- Lights up in Deice Mode(for Heat pump model) OUT DOOR --- Lights up in Compressor operation(for Cooling model) Health Dehumidification Operation • Intermittent operation of fan at low speed. Sleep Mode Auto Control • The fan is switched to low(Cooling), med(Heating) speed. • The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours. Natural Air Control by CHAOS Logic • The fan is switched to intermittent or irregular operation • The fan speed is automatically switched from high to low speed. Airflow Direction Control • The louver can be set at the desired position or swing up and down automatically. 18 Multi Air Conditioner Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during deicing. • Hot start after deice ends. Hot-start Control (Heating) • The indoor fan stops until the evaporator piping temperature will be reached at 22°C. Functions Remote Controller Operation ON/OFF Operation Mode Selection Cooling Operation Mode.( (Cooling (Heating model only) model only) ) Auto Operation Mode.( Healthy Dehumidification Operation Mode.( ) Heating Operation Mode.( ) ) Fan Speed Selection (Low) (Med) (High) (CHAOS) Room, Temperature Display : (High:39°C Low:11°C) Temperature Setting TEMPERATURE LOW HIGH Down to 18°C Up to 30°C Cooling Heating Down to 16°C Up to 30°C JET COOL PLASMA(Option)/NEGATIVE ION(Option) PLASMA Setting the Time or Timer Timer Selection ON OFF Timer Setting SET : OFF, ON, OFF ON Timer Cancel CANCEL Sleep Operation : Cancel Sleep Mode, Timer ON or Timer OFF Airflow Direction Control : 1, 2, 3, 4, 5, 6, 7, Off Timer Fan Operation Mode : Fan Operates without cooling or heating. Horizontal Airflow Direction Control Button(Option) Reset Service Manual 19 Display Function Display Function 1. Heating Model 2. Cooling Model Operation Indicator Operation Indicator • Cooling, Soft Dry, Fan, Heating Sleep Timer Indicator • Cooling, Soft Dry, Fan Sleep Timer Indicator • Sleep Mode • Sleep Mode Timer Indicator Timer Indicator • Timer Mode • Timer Mode Compressor on Indicator Defrost Indicator OUT DOOR • Hot-start, Defrost Self-diagnosis Function ■ Error Indicator • The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble. • Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table. • If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed. • After error occurrence, if error is released, error LED is also released simultaneously. • To operate again on the occurrence of error code 12, be sure to pull out power cord and then re-insert. • Having or not of error code is different from Model. Error Code Error LED (Indoor body operation LED) (once) 1 3sec 3sec 3sec 2 3sec (3times) 3 3sec • Indoor suction temperature thermistor open/short. • Indoor pipe temperature thermistor open/short. SVC check point • Indoor TH ass'y check • Outdoor suction temperature thermistor open/short. • Outdoor TH ass'y • Outdoor pipe temperature check thermistor open/short. (twice) 3sec Error contents 3sec • Abnormal operation of multi product. • Resetting of remocon (Simultanueous operation of operating mode cooling and heating) (5times) 5 • Poor communication • Communication line/circuit check • Indoor fan lock • Check indoor fan motor and outdoor PCB ass'y 3sec 8 20 Multi Air Conditioner Operation Details Operation Details Main Unit Function 1) C/O Model Operation Indicator • On while in appliance operation, off while in appliance pause • Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on) Sleep Timer Indicator • On while in sleep timer mode, off when sleep timer cancel or appliance operation pause Timer Indicator • On while in timer mode (on/off), off when timer mode is completed or canceled. Comp. Running Incidator • While in appliance operation, on while in outdoor unit compressor running, off while in compressor off 2) H/P Model Operation Indicator • On while in appliance operation, off while in appliance pause • Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on) Sleep Timer Indicator • On while in sleep timer mode, off when sleep timer cancel or appliance operation pause Timer Indicator • On while in timer mode (on/off), off when timer mode is completed or canceled Defrost Indicator • Off except when hot start during heating mode operation or while in defrost control ■ Cooling Mode Operation • When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan stop. • When it reaches 0.5°C above the setting temp, they start to operate again. Compressor ON Temp ➲ Setting Temp+0.5°C Compressor OFF Temp ➲ Setting Temp-0.5°C • While in compressor running, operating with the airflow speed set by the remote control. While in compressor not running, operating with the low airflow speed regardless of the setting. ■ Healthy Dehumidification Mode • When the dehumidification operation input by the remote control is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature. 26°C ≤ Intake Air Temp ➲ 25°C 24°C ≤ Intake Intake Air Temp<26°C ➲ Intake Air Temp-1°C 18°C ≤ Intake Intake Air Temp<24°C ➲ Intake Air Temp-0.5°C Intake Air Temp<18°C ➲ 18°C Service Manual 21 Operation Details • While in compressor off, the indoor fan repeats low airflow speed and pause. • While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification operation and 4-min compressor off repeat. Compressor ON Temp. ➲ Setting Temp+0.5°C Compressor OFF Temp. ➲ Setting Temp-0.5°C • In 10-min dehumidification operation, the indoor fan operates with the low airflow speed. ■ Heating Mode Operation(H/P model) • When the intake air temp reaches +3°…above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on. Compressor ON Temp. ➲ Setting Temp. Compressor OFF Temp. ➲ Setting Temp.+3°C • While in compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 28°C , it operates with the low or setting airflow speed. When the indoor pipe temp is between 20°C and 28°C, it operates with Super-Low(while in sleep mode, with the medium airflow speed). • While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C , it operates with the low airflow speed. • If overloaded while in heating mode operation, in order to prevent the compressor from OLP operation, the outdoor fan is turned on/off according to the indoor pipe temp. • While in defrost control, both of the indoor and outdoor fans are turned off. ■ Defrost Control(H/P model) • Defrost operation is controlled by timer and sensing temperature of outdoor pipe. • The first defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from starting of heating operation and more than 10 minutes operation of compressor. • Defrost ends after 9/6 minutes passed from starting of defrost operation or after the outdoor fan operates within max. 2 minutes 30 seconds when the outdoor pipe temperature rises over 12°C even it before 12 minutes. • The second defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from ending of the first defrost and more than 10 minutes operation of compressor. ■ Cooling overload • Control indoor fan by sensing outdoor pipe temperature. • One step down from setting fan speed if pipe temperature is oven 50°C and if below 45°C, operate on setting temperature. • One of the outdoor fan is OFF if pipe temperature is below 0°C and outdoor fan is ON if pipe temperature is over 0°C. ■ Heating overload(H/P models) • Outdoor fan ON/OFF by sensing outdoor pipe temperature. • Outdoor fan is OFF if pipe temperature is over 6.5°C and outdoor fan is ON if pipe temperature is below 0°C. • Outdoor fan is off if any one part is heating overload condition. 22 Multi Air Conditioner Operation Details ■ Fuzzy Operation (C/O Model) • According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on. Compressor ON Temp ➲ Setting Temp + 0.5°C Compressor OFF Temp ➲ Setting Temp + 0.5°C • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 26°C ≤ Intake Air Temp ➲ 25°C 24°C ≤ Intake Air Temp < 26°C ➲ Intake Air Temp + 1°C 22°C ≤ Intake Air Temp < 24°C ➲ Intake Air Temp + 0.5°C 18°C ≤ Intake Air Temp < 22°C ➲ Intake Air Temp Intake Air Temp<18°C ➲ 18°C • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature. ■ Fuzzy Operation (H/P Model) • When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since the operation off, the operation mode is selected. • When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air temp at that moment as follows. 24°C ≤ Inatake Air Temp ➲ Fuzzy Operation for Cooling 21°C ≤ Inatake Air Temp<24°C ➲ Fuzzy Operation for Dehumidification Inatake Air Temp<21°C ➲ Fuzzy Operation for Heating • If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10 sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated. 1) Fuzzy Operation for Cooling • According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on. Compressor ON Temp ➲ Setting Temp +0.5°C Compressor OFF Temp ➲ Setting Temp + 0.5°C • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 26°C≤ Intake Air Temp ➲ 25°C 24°C≤ Intake Air Temp<26°C ➲ Intake Air Temp + 1°C 22°C≤ Intake Air Temp<24°C ➲ Intake Air Temp + 0.5°C 18°C≤ Intake Air Temp<22°C ➲ Intake Air Temp Intake Air Temp<18°C ➲ 18°C • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature. Service Manual 23 Operation Details 2) Fuzzy Operation for Dehumidification • According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on. Compressor ON Temp ➲ Setting Temp + 0.5°C Compressor OFF Temp ➲ Setting Temp+0.5°C • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 26°C ≤ Intake Air Temp ➲ 25°C 24°C ≤ Intake Air Temp<26°C ➲ Intake Air Temp+1°C 22°C ≤ Intake Air Temp<24°C ➲ Intake Air Temp+0.5°C 18°C ≤ Intake Air Temp<22°C ➲ Intake Air Temp Intake Air Temp<18°C ➲ 18°C • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in dehumidification operation. 3) Fuzzy Operation for Heating • According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on. Compressor ON Temp ➲ Setting Temp Compressor OFF Temp ➲ Setting Temp + 3°C • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 20°C≤Intake Air Temp ➲ Intake Air Temp + 0.5°C Intake Air Temp<20°C ➲ 20°C • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the intake air temperature and the setting temperature. ■ Airflow Speed Selection • The airflow speed of the indoor fan is set to high, medium, low, or chaos (auto) by the input of the airflow speed selection key on the remote control. ■ On-Timer Operation • When the set time is reached after the time is input by the remote control, the appliance starts to operate. • The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached. • If the appliance is operating at the time set by the timer, the operation continues. 24 Multi Air Conditioner Operation Details ■ Off-Timer Operation • When the set time is reached after the time is input by the remote control, the appliance stops operating. • The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached. • If the appliance is on pause at the time set by the timer, the pause continues. ■ Off-Timer <=> On-Timer Operation • When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is carried out according to the set time. ■ Sleep Timer Operation • When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appliance operation, the operation of the appliance stops. • While the appliance is on pause, the sleep timer mode cannot be input. • While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by 1°C. After another 30 min elapse, it increases by 1°C again. • When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to the low. • When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium. ■ Chaos Swing Mode • By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they are fixed to the desired direction. • While in Chaos Swing mode, the angles of cooling and heating cycle operations are different. ■ Chaos Natural Wind Mode • When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the airflow mode is operated for 2~15 sec. randomly by the Chaos Simulation. ■ Jet Cool Mode Operation (C/O Model) • If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates. • In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation. • In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C • When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority. • When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then operated in order that the air outflow could reach further. ■ Jet Cool Mode Operation (H/P Model) • While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated. • In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation. • In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C. • When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority. • When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then operated in order that the air outflow could reach further. Service Manual 25 Operation Details ■ Forced Operation • Operation procedures when the remote control can't be used. • The operation will be started if the power button is pressed. • If you want to stop operation, re-press the button. Cooling Model Operating mode Indoor FAN Speed Setting Temperature Heat pump Model Room Temp. ≥ 24°C 21°C ≤ Room Temp. < 24°C Room Temp. < 21°C Cooling High 22°C Cooling High 22°C Healthy Dehumidification High 23°C Heating High 24°C • While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to indicate the forced operation. ■ Test operation • During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room temperature and resets in 18±1 minutes. • During test operation, if remote controller signal is received, the unit operates as remote controller sets. If you want to use this operation, open the front panel upward and Press the power button let it be pressed for about 3 seconds. • If you want to stop the operation, re-press the button. ■ Auto restart • In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate procedures automatically to the previous operating conditions. ■ Air Cleaner Operation • When an air cleaner function is selected during Air Conditioner operation - Plasma air cleaner function will be operated while in any operation mode with selecting the function. - The function is to be stopped while it is operating with selecting the function. • When an air cleaner function is selected during operation off - The function will be only operated. • When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B) will be operated again. 26 Multi Air Conditioner Operation Details ■ Remote Control Operation Mode • When the remote control is selected by the slide switch on the main unit, the appliance operates according to the input by the remote control. ■ Protection of the evaporator pipe from frosting • If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cooling cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor evaporator pipe from frosting. • When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the outdoor fan is turned on according to the condition of the room temperature. ■ Buzzer Sounding Operation • When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds. • When the appliance-pause key is input by the remote control, the long "beep—" sounds. • When a key is input by the remote control while the slide switch on the main unit of the appliance is on the forced operation position, the error sound "beep-beep-beep-beep-beep-" is made 10 times to indicate that the remote control signal cannot be received. Service Manual 27 2-way, 3-way Valve 2-way, 3-way Valve 2-way Valve (Liguid Side) 3-way Valve (Gas Side) Valve cap Flare nut Hexagonal wrench (4mm) Open position Closed position To piping connection Flare nut Open position Closed position Pin To piping connection To outdoor unit Service Service port cap port To outdoor unit Works Shaft position Shaft position Service port Shipping Closed (with valve cap) Closed (with valve cap) Closed (with cap) Air purging (Installation) Open (counter-clockwise) Closed (clockwise) Open (push-pin or with vacuum pump) Operation Open (with valve cap) Open (with valve cap) Closed (with cap) Pumping down (Transfering) Closed (clockwise) Open (counter-clockwise) Evacuation (Servicing) Open Open 3. Open (with charging cylinder) Open Open 4. Gas charging (Servicing) Open (with charging cylinder) Pressure check (Servicing) Open Open 5. Open (with charging cylinder) Gas releasing (Servicing) Open Open 6. Open (with charging cylinder) 1. 2. 28 Multi Air Conditioner Open (connected manifold gauge) 2-way, 3-way Valve (1) Pumping down Liquid side Indoor unit 2-Way valve Close Outdoor unit Gas side 3-Way valve Open manifold gauge Low-handle (CLOSE) Hi- handle (CLOSE) • Procedure 1. Confirm that both the gas side and liquid side valves are set to the open position. - Remove the valve stem caps and confirm that the valve stems are in the raised position. - Be sure to use a hexagonal wrench to operate the valve stems. 2. Operate the unit for 10 to 15 minutes. 3. Stop operation and wait for 3 minutes, then connect the manifold gauge to the service port of the gas side valve. - Connect the hose of the gauge with the push pin to the service port. 6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg/cm g. 2 7. Immediately set the gas side valve to the closed position. - Do this quickly so that the gauge ends up indig. cating 1kg/ 8. Disconnect the charge set, and mount the liquid side and gas side valve caps and the service port nut. - Use torque wrench to tighten the service port nut to a torque of 1.8kg.m.(4.2kg*m/5.5kg*m) - Be sure to check for gas leakage. 4. Air purging of the charge hose. - Open the Low-handle valve on the gauge slightly to air purge from the hose. 5. Set the liquid side valve to the closed position. Service Manual 29 2-way, 3-way Valve (2) Evacuation (All amount of refrigerant leaked) Indoor unit Liquid side 2-Way valve Close Outdoor unit Gas side 3-Way valve Open manifold gauge Vacuum pump Lowhandle (OPEN) Hi- handle (CLOSE) • Procedure 1. Confirm that both the liguid side valve and gas side valve are set to the opened position. 2. Connect the vaccum pump to the center hose of the manifold gauge. 3. Connect the service port of the gas side valve to the low side of the gauge. 4. Connect power supply to outdoor unit. 5. Evacuation for approximately one hour. - Confirm that the gauge needle has moved toward-76 cmHg (vacuum of 4 mmHg or less). 6. Close the Low handle of the gauge turn off the vacuum pump, and confirm that the gauge needle does not move(approximately 5 minutes after turning off the vacuum pump). 30 Multi Air Conditioner 7. Disconnect the charge hose from the vacuum pump. - Vacuum pump oil. If the vacuum pump oil becomes dirty or depleted,replenish as needed. 8. Mount the valve caps and the service port caps. 2-way, 3-way Valve (3) Gas Charging (After Evacuation) Liquid side Indoor unit 2-Way valve Close Outdoor unit Gas side 3-Way valve Charging cylinder Open manifold gauge Low-handle Check valve (OPEN) Hi- handle (CLOSE) • Procedure 1. Connect the gauge to the charging cylinder. - Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. - If you are using a gas cylinder, also use a scale and reverse the cylinder so that the system can be charged with liquid. 2. Purge the air from the charge hose. - Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air. (Be careful of the liquid refrigerant). The procedure is the same if using a gas cylinder. 3. Open the low handle on the gauge and charge the system with liquid refrigerant. - If the system can not be charged with the specified amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure(pumping down-pin). 4. Immediately disconnect the charge hose from the gas side valve's service port. This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner. - Stopping partway will allow the gas to be discharged. - If the system has been charged with liquid refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose. 5. Mount the valve stem nuts and the service port nut. - Use torque wrench to tighten the service port nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.) - Be sure to check for gas leakage. Service Manual 31 Cycle Troubleshooting Guide Cycle Troubleshooting Guide Trouble analysis 1. Check temperature difference between intake and discharge air and operating current. Temp. difference Current : approx. 0°C : less than 80% of rated current All amount of refrigerant leaked out. Check refrigeration cycle. Temp. difference Current : approx. 8°C : less than 80% of rated current Refrigerant leakage Clog of refrigeration cycle Defective compressor Temp. difference Current : less than 8°C : over the rated current Temp. difference : over 8°C Temp. Difference Operating Current Excessive amount of refrigerant Normal Notice: Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger. 2. Check temperature and pressure of refrigeration cycle. Suction pressure (Compared with the normal value) Temperature (Compared with the normal value) High Cause of Trouble Description Defective compressor Defective 4-way reverse valve Current is low. Excessive amount of refrigerant High pressure does not quickly rise at the beginning of operation. Insufficient amount of refrigerant(Leakage) Clogging Current is low. Higher Normal Lower Higher Current is low. Notice: 1. The suction pressure is usually 4.5~6.0 kg/cm G at normal condition. 2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty. 2 32 Multi Air Conditioner Electronic Parts Troubleshooting Guide Electronic Parts Troubleshooting Guide 1. The Outdoor Unit does not operate at all (* Refer to Electronic Control Device drawing and Schematic diagram.) Turn off Main Power (After 10 seconds) Turn on Main Power Does "beeping" sound is made from the Indoor Unit? YES NO Check the voltage of power(About AC 220V/AC240V, 50Hz) Primarily, the operating condition of Micom is OK. • Main power's voltage • Voltage applied to the unit • Connecting method of Indoor/Outdoor connecting cable • Check Fuse (Outdoor PCB Ass'y) • Check Varistor ZNRØ1J(Outdoor PCB Ass'y) Check each load(Indoor/Outdoor Fan Motor, Compressor, Stepping Motor etc.) and contacting condition of related connector Check the connection housing for contacting • Connector related to CN-POWER • Display PWB Ass'y Check PCB Board Operation Check Content Items • Power Transformer (Outdoor unit) - Input Voltage - Output Voltage Remedy - About AC220V/240V±10% - Check the power voltage - About AC14±3V • Replace Trans • DC +12V • IC01D(7812) Output (Indoor/Outdoor unit) • Replace IC01D • DC +5V • IC02D(7805) Output (Indoor/Outdoor unit) • IC01A(KIA7036, Reset IC) X01(8MHz) • Replace IC02D • Voltage of Micom No. 2, (DC +4.5V over) and Soldering condition. • Replace faulty parts Service Manual 33 Electronic Parts Troubleshooting Guide 2. The product is not operate with the remote controller. Turn on Main Power While the compressor has been stopped, the compressor does not operate owing to the delaying function for 3 minutes after stopped. When the compressor stopped Indoor Fan is driven by a low speed. At this point the wind speed is not controlled by the remote controller. (When operated in the Sleeping Mode, the wind speed is set to the low speed by force.) Cause by the remote control When the mark( battery. ) is displayed in LCD screen, replace When the detect switch(double key) inside the remote controller door is fault, it is impossible to operate temperature regulating(▲/▼) and wind speed selecting. Check the connecting circuit between the remote controller MICOM (No. ) - R17(2Ω) - IR LED - Q1 R16(2.2KΩ). 34 Multi Air Conditioner Caused by other parts except the remote control Check the contact of CN-DISPI connector. Check DISP PWB Ass'y - Voltage between CN DISP1 ① - ⑦ : DC +5V Check point • Check the connecting circuit between PIN ②R01L(1K) - C01L(680PF) - MICOM PIN • Check Receiver Ass'y Electronic Parts Troubleshooting Guide 3. When cooling does not operate Turn on Main Power Operate "Cooling Mode( )" by setting the desired temperature of the remote controller is less than one of the indoor temperature by 1°C at least. When in Air Circulation Mode, Compressor/Outdoor Fan is stopped. Check the sensor for indoor temperature is attached as close as to be effected by the temperature of Heat Exchanger(EVA). When the sensor circuit for indoor temperature and connector are in bad connection or are not engaged, Compressor/Outdoor Fan is stopped. • Check the related circuit of R02H(12.1K), R01H(1.0K), R04H(6.2K), R03H(1.0K) (Indoor unit). • Check the indoor temperature sensor is disconnected or not(About 10kΩ / at 25°C). Check Relay(RY - COMP) for driving compressor. • When the power(About AC220V/240V) is applied to the connecting wire terminal support transferred to compressor, PWB Ass'y is normal. • Check the circuit related to the relay. Check point Between two pin of DC part in relay for COMP COMP ON COMP OFF Below DC 1V (app) About DC12V Check Outdoor Unit Service Manual 35 Electronic Parts Troubleshooting Guide 4. When indoor Fan does not operate Turn off Main power Check the connection of CN-FAN or CN-MOTOR Check the Fan Motor Check the Fuse(AC250V/T2A) Check the related circuit of indoor Fan Motor. • The pin of Micom, and the part for driving SSR • Check the pattern • Check the SSR - SSR Open: Indoor Fan Motor never operate - SSR short: Indoor Fan Motor always operates in case of ON or OFF. Turn ON Main Power Check the SSR high speed operation by remote control. (The Indoor Fan Motor is connected) The voltage of PIN NO 1(blue) and 3(yellow) of CN-FAN or CN-MOTOR. About AC 180V over About AC 50V over SSR is not damaged SSR Check 36 Multi Air Conditioner Electronic Parts Troubleshooting Guide 5. When Vertical Louver does not operate. • Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor. • If the regular torque is detected when rotating the Vertical Louver with hands ⇒ Normal • Check the connecting condition of CN-U/D Connector • Check the soldering condition(on PWB) of CN-U/D Connector Check the operating circuit of the Vertical Louver • Confirm that there is DC +12V between pin ①(RED) of CN-U/D and GND. If there are no problems after above checks • Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver Service Manual 37 Electronic Parts Troubleshooting Guide 6. When Heating does not operate Turn ON Main Power Operate “Heating Mode( )” by setting the desired temperature of the remote control is higher than one of the indoor temperature by 2°C at least. In heating Mode, the indoor fan operates in case the pipe temperature is higher than 28°C. Check the connector of intake and pipe sensor(thermistors) • Check the related circuit of R02H(12.1K), R01H(1.0K), R04H(6.2K), R03H(1.0K). • Check the indoor room temperature is disconnected or not (about 10KΩ/at 25°C). • Check the indoor pipe temperature is disconnected or not (about 5KΩ/at 25°C). Check the DC voltage on the PWB ASS’Y • The details of check are as followings • Comp Relay. Check point • 4-Way Relay Comp ON Between two pin of DC part in relay Below DC 1V for COMP. Comp OFF About DC 12V Check point 4-Way OFF Between two pin of DC part in relay Below DC 1V About DC 12V for 4-way. Check Outdoor Unit 38 Multi Air Conditioner 4-Way ON Electronic Parts Troubleshooting Guide 7. Outdoor unit does not operate at all. Check Outdoor Unit PCB Board Operation Check in Outdoor Content Items • Power Transformer (Outdoor unit) - Input Voltage - Output Voltage Remedy - About AC220V/240V±10% - Check the power voltage • Replace Trans - About AC14±3V • DC +12V • Replace IC01D • DC +5V • Replace IC02D • IC01D(7812) Output (Indoor/Outdoor unit) • IC02D(7805) Output (Indoor/Outdoor unit) • Replace faulty parts • IC01A(KIA7036, Reset IC) X01(8MHz) Turn off Main Power • Check the electrical wiring diagram of outdoor side. • Check the abnormal condition for the component of Compressor/Outdoor Fan Motor/4-way. • Check the “open” or “short” of connecting wires between indoor and outdoor. 8. Communication error • The control data can be transmitted or received between indoor and outdoor unit with one signal cable. • If the data be disturbed by any noise level and misconnection, the unit will be operated incorrectly. In this case, the indoor unit blinks the operation and operation LED on display and indoor fan, outdoor fan, COMP are not operated. • The unit can be reoperated by On/Off control of Remocon. Service Manual 39 Installation Installation (1) Installation of Indoor, Outdoor unit 1) Selection of the best location Front 1. Indoor unit • There should not be any heat source or steam near the unit. • There should not be any obstacles to prevent the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles. 2. Outdoor unit • If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted. • There should not be any animals or plants which could be affected by hot air discharged. • Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles. Left Rear left Down right Right Rear right More than 5 cm More than 5 cm More than 5 cm More than eye-level More than 20 cm More than 20 cm More than 70 cm 3. Piping length and the elevation Indoor unit Pipe Size Capacity (Btu/h) GAS 10, 12K 1/2"(3/8") LIQUID Max. piping length A (m) Max. Elevation B (m) 1/4" 15 7 A B Outdoor unit 40 Multi Air Conditioner Installation 2) Indoor Unit Installation The mounting wall should be strong and solid enough to protect it from the vibration. marking-off line Thread Weight The lower left and the right side of Installation Plate Left rear piping Right rear piping 20mm 40mm 50mm ø70mm ø70mm Wall Indoor Outdoor 5~7mm 2. Drill the piping hole with 70mm dia. holecore drill. • Line according to the arrows marked on lower the left and the rght side of the Installation Plate. The meeting point of the extended line is the center of the hole. • Drill the piping hole at either the right or the left and the hole should be slightly slant to the outdoor side. Type "A" screw 40mm 1. Mount the installation plate on the wall with four Type "A" screws. (If mounting the unit on the concrete wall, consider using anchor bolts.) • Always mount the Installation plate horizontally by aligning the marking-off line by means of the thread and a level. Installation Plate Service Manual 41 Installation (2) Piping and Drainage of Indoor Unit 1) Preparation of pipings Pipe cutter 1. Cut the pipes and the cable. • Use the accessory piping kit or the pipes purchased locally. • Measure the distance between the indoor and the outdoor unit. • Cut the pipes a little longer than the measured distance. • Cut the cable 1.5m longer than the length of the pipe. Reamer Point down "A"; ø12.7 mm (1/2") ø9.52 mm (3/8") ø6.35 mm (1/4") → 0~0.5 mm → 0~0.5 mm → 0~0.5 mm Handle Bar Bar Copper pipe Yoke "A" 3. Flaring the pipes. • Insert the flare nuts, mounted on the connection ports of both indoor and outdoor unit, onto the copper pipes. Some refrgerant gas may leak, when the flare nuts are removed from the indoor unit, as some gas is charged to prevent the inside of the pipe from rusting. • Fit the copper pipe end into the Bar of flare tool about 0~0.5mm higher. (See illustration) • Flare the pipe ends. Rough Pipe 2. Remove burrs. • Remove burrs from cut edges of pipes. • Turn the pipe end toward down to avoid the metal powder entering the pipe. Caution: If burrs are not removed, they may cause a gas leakage. Slanted 90 Cone Clamp handle Red arrow mark = Improper flaring = 4. Tape the flaring portion to protect it from the dust or damages. Inclined Surface damaged Cracked Uneven thickness When properly flared, the internal surface flare will evenly shine and be of even thickness. Since the flare part comes into contact with the connectors, carefully check the flare finish. 42 Multi Air Conditioner Installation 2) Connection of Pipings Installation plate 1. Remove the installation plate • Pull the two '∆' marked portion of bottom of the chassis and pull the installation plate out of chassis. Pull 2. Route the drain hose and the indoor tubing. Pull For left rear piping 3. Route the tubing and the drain hose straight backwards(see figure). 4. Insert the connecting cable into the indoor unit through the piping hole. • Do not connect the cable to the indoor unit. • Make a small loop with the cable for easy connection later. Tubing holder • To remove the holder, press the bottom of the chassis near the holder upwards and the tab is clear of its hole. • Turn it clockwise approx. 90° and remove it. Pull Press 5. Tape the tubing, drain hose and the connecting cable. Be sure that drain hose locates at the lowest side of the bundle. Locating at the upper side can be a reason that drain water overflows drain pan inside the unit. Gas side piping Connecting cable Liquid side piping Drain hose Service Manual 43 Installation 6. Indoor unit installation. • Hook the indoor unit onto the upper position of the installation plate. (Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure the hooks are properly seated on the installation plate by moving it in left and right. Connecting cable Drain hose Press the lower left and right side of the unit against the Installation Plate until the hooks engage with their slots (sound click). 7. Connecting the pipings to the indoor unit. • Align the center of the pipings and sufficiently tighten the flare nut with fingers. • Finally, tighten the flare nut with torque wrench until the wrench clicks. Wrench tightening the flare nut with forque wrench, ensure the direction for tightening follows the arrows on the wrench. Pipe Size Torque Liquid Side (1/4") 1.8kg m Liquid Side (3/8") 4.2kg m Gas Side (1/2") 5.5kg m Gas Side (5/8") 6.6kg m 8. Wrap the insulation material around the connecting portion. CAUTION: Take care to arrange the pipings, drain hose and cables as the right upper picture for inserting it into the indoor unit and refixing the tubing holder easily. 44 Multi Air Conditioner Indoor unit tubing Flare nut Pipings Spanner Torque wrench Plastic bands Insulation material Wrap the insulation material around the connecting portion. Installation 9. Set the pipings and the connecting cable to the back of the chassis with the tubing holder. • Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged in the bottom of chassis. Drain hose Taping Piping Tubing holder 1 Hook 2 Push 10. Indoor unit installation. • Hook the indoor unit onto the upper portion of installation plate. (Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure the hooks are properly seated on the installation plate by moving it in left and right. Connecting cable Drain hose Press the lower left and right side of the unit against the Installation Plate until the hooks engages with their slots (sound click). Service Manual 45 Installation (3) Connecting Pipings and the cable to Outdoor unit 1) Connecting the pipings to the Outdoor unit 1. Align the center of the pipings and sufficiently tighten the flare nut with fingers. 2. Finally, tighten the flare nut with torque wrench until the wrench clicks. • When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench. Pipe Size Torque Liquid Side (1/4") 1.8kg m Liquid Side (3/8") 4.2kg m Gas Side (1/2") 5.5kg m Gas Side (5/8") 6.6kg m A-UNIT Outdoor unit Gas side piping B-UNIT Liquid side piping Torque wrench CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of control box cover. 2) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Specification of power source. 5) Confirm that electrical capacity is sufficient. 6) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Never fail to equip a leakage breaker where it is wet or moist. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. • Proper starting power is not given to the compressor. 46 Multi Air Conditioner Installation 2) Connection of the cable Outdoor unit 1. Remove the cover control from the unit by loosening the screw. Connect the wires to the terminals on the control board individually as the following. Terminal block Over 5mm Holder for power supply cord • L2-C242GL0 1(L) 2(N) Terminal on the OUTDOOR UNIT 3 3 2(N) 1(L) 1(L) 2(N) Cover control Connecting cable Power Cord Power cord 3 2(N) 1(L) Terminal on the INDOOR UNIT B-UNIT 3 2(N) 1(L) Terminal on the INDOOR UNIT A-UNIT 2. Secure the cable onto the control board with the holder (clamper). 3. Refix the cover control to the original position with the screw. 4. Use a recongnized circuit breaker between the power source and the unit. A disconnection device to adequately disconnect all supply lines must be fitted. • L2-H242GL0 1(L) 2(N) Terminal on the OUTDOOR UNIT 3 3 2(N) 1(L) 1(L) 2(N) Power Cord 1(L) 2(N) 3 4 Terminal on the INDOOR UNIT A-UNIT 1(L) 2(N) 3 4 Terminal on the INDOOR UNIT A-UNIT CAUTION GN /YL 20 mm CAPACITY (Btu/h) NORMAL CROSSSECTION AREA ~24K 2.5mm2 ~36K 3.5mm2 ~48K 5.5mm The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Rubber insulation, type H07RN-F approved by HAR or SAA). ø7.5mm ø8.5mm The power cord connected to the outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA). GN /YL Models NORMAL CROSSSECTION AREA L2-C242GL0 1.5mm2 Others 0.75mm2 2 20 mm Service Manual 47 Installation CAUTION If a power plug is not to be used, provide a circuit breaker between power source and the unit as shown below. Main power source Air Conditioner Circuit Breaker Use a circuit breaker or time delay fuse. Connect the cable to the indoor unit 1. Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively. (Refer to Wiring diagram on page12.) WARNING • Be sure to refer to the wiring diagram label inside the cover control and carry out the correct field wiring. Wrong wiring can cause the unit to misoperate to result in a fire hazard. • Check local electrical codes and any specified wiring instructions or limitations. 2. Attach the Grille onto the cabinet. • Grasp lower the left and right side of the Grille and engage four tabs on the top inside edge of the chassis. • Press the Grille toward the chassis until it will be back into place. 48 Multi Air Conditioner Connecting cable Installation (4) Checking the drainage 1. To remove the front panel from the indoor unit, remove the front panel from the indoor unit cabinet. ■ Set the air direction louvers up-and-down to the position(horizontally) by hand. ■ Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille toward you and lift it off. (5) Form the piping 1. Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tapes. ■ If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately. 2. In cases where the outdoor unit is installed below the indoor unit perform the following. ■ Tape the piping, drain hose and connecting cable from down to up. ■ Secure the tapped piping along the exterior wall using saddle or equivalent Pull the right and the left side. Screw Drain hose 2. To check the drainage. ■ Pour a glass of water on the evaporator. ■ Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit. Taping Pipings Plastic band Connecting cable Power cord • Trap is required to prevent water from entering into electrical parts. 3. Drain piping ■ The drain hose should point downward for easy drain flow. 3. In cases where the Outdoor unit is installed above the Indoor unit perform the following. ■ Tape the piping and connecting cable from down to up. ■ Secure the taped piping along the exterior wall. Form a trap to prevent water entering the room. ■ Fix the piping onto the wall by saddle or equivalent. Seal a small opening around the pipings with gum type sealer. Downward slope ■ Do not make drain piping. Do not raise Water leakage Accumulated drain water Air Water Waving leakage Trap Tip of drain hose dipped in water Water leakage Less than 50mm gap Ditch Trap Service Manual 49 Installation (6) Air Purging of the Pipings and indoor unit The air which contains moisture remaining in the is refrigeration cycle may cause a malfunction on the compressor. 1. Confirm that both the liquid side valve and the gas side valve are set to the closed position. 2. After connecting the piping, check the joints for gas leakage with gas leak detector. 3. Remove the service port nut, and connect the gauge manifold and the vacuum pump to the service port by the charge hose. 4. Vacuum the indoor unit and the connecting pipes until the pressure in them lowers to below-76cmHg. 5. Disconnect the charge hose and fit the nut to the service port. (Tightening torque: 1.8kg.m) 6. Remove the valve stem nuts, and fully open the stems of the 2-way and 3-way valves with a hexagon wrench. 7. Tighten the valve stem nuts of the 2-way valve and 3-way valve. Indoor unit Liquid side Closed 2-way valve Gas side 3-way valve Vacuum pump OPEN 50 Multi Air Conditioner CLOSE Closed Outdoor unit Installation (7) Maximum Length of Pipe and Freon Extra Charge Charge amount per 1m CONNECTION TYPE Capacity (Btu/h) STANDARD LENGTH(m) A B C D Charge am't(g) per 1m ~7000 7.5 7 15 7 15 20 ~9000 7.5 7 15 7 15 20 ~12000 7.5 7 15 7 15 20 ~18000 7.5 10 20 10 20 20 ~24000 7.5 15 30 15 30 30 B(Length) INDOOR UNIT A(Height) OUTDOOR UNIT C(Height) INDOOR UNIT D(Length) ** A, B mean indoor unit higher located than outdoor unit. C, D mean outdoor unit higher located than indoor unit. CAUTION: Capacity is based on standard length and maximum allowance length is on the basis of reliability. Oil trap should be installed every 5~7 meters (16.4~23.0ft). Service Manual 51 Installation (8) Test running 1) Connection of power supply 1. Connect the power supply cord to the independent power supply. 2. Prepare the remote control. • Insert two batteries provided. Remove the battery cover from the remote controller. • Slide the cover according to the arrow direction. Insert the two batteries. (Two "R03" or "AAA" dry-cell batteries or equivalent.) • Be sure that the (+) and (-) directions are correct. • Be sure that both batteries are new. Re-attach the cover. • Slide it back into position. 3. Operate the unit at cooling operation mode for fifteen minutes or more. Battery Cover Settlement of Outdoor Unit Bolt • Anchor the outdoor unit with a bolt and nut (ø10cm) tightly and horizontally on a concrete or rigid mount. • When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake. • In the case when the vibration of the unit is conveyed to the house, settle the unit with an antivibration rubber. Tubing connection 2) Evaluation of the performance 1. Measure the temperature of the intake and discharge air. 2. Ensure the difference between the intake temperature and the discharge one is more than 8°C. Discharge air 52 Multi Air Conditioner Operation Operation (1) Name and Function-Remote Control (Cooling Models) Remote Controller 1 ON/OFF TIMER BUTTONS Used to set the time of starting and stopping operation. 2 TIME SETTING BUTTONS Used to adjust the time. 3 TIMER SET/CANCEL BUTTONS Used to set the timer when the desired time is obtained and to cancel the Timer operation. 4 SLEEP MODE AUTO BUTTON Used to set Sleep Mode Auto operation. 5 AIR CIRCULATION BUTTON Used to circulate the room air without cooling or heating (turns indoor fan on/off). 6 ROOM TEMPERATURE CHECKING BUTTON Used to check the room temperature. 7 PLASMA(OPTION) Used to start or stop the plasma-purification function. NEGATIVE ION(OPTION) Used to generate negative ion. 8 HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON (NOT ON ALL MODELS) Used to set the desired horizontal airflow direction. 9 RESET BUTTON Used prior to resetting time or after replacing batteries. Signal transmitter. Transmits the signals to the room air conditioner. Signal transmitter ON OFF 4 1 5 2 SET CANCEL 3 6 PLASMA(or ) 7 8 9 Service Manual 53 Operation (2) Name and Function-Remote Control (Heat Pump Models) Remote Controller ON/OFF TIMER BUTTONS Used to set the time of starting and stopping operation. Signal transmitter. 1 Transmits the signals to the room air conditioner. 2 TIME SETTING BUTTONS Used to adjust the time. 3 TIMER SET/CANCEL BUTTONS Used to set the timer when the desired time is obtained and to cancel the Timer operation. Signal transmitter 4 5 6 ON 7 OFF 4 1 5 2 SET SLEEP MODE AUTO BUTTON Used to set Sleep Mode Auto operation. AIR CIRCULATION BUTTON Used to circulate the room air without cooling or heating (turns indoor fan on/off). ROOM TEMPERATURE CHECKING BUTTON Used to check the room temperature. PLASMA(OPTION) Used to start or stop the plasma-purification function. NEGATIVE ION(OPTION) Used to generate negative ion. CANCEL 3 6 PLASMA(or ) 7 8 8 HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON (NOT ON ALL MODELS) Used to set the desired horizontal airflow direction. 9 RESET BUTTON Used prior to resetting time or after replacing batteries. 9 54 Multi Air Conditioner Disassembly of the parts (Indoor unit) Disassembly of the parts (Indoor unit) Warning : Disconnect the unit from power supply before making any checks. Be sure the power switch is set to “OFF”. To remove the Grille from the Chassis. • Set the up-and-down air discharge louver to open position (horizontally) by finger pressure. • Remove the securing screws • To remove the Grille, pull the lower left and right side of the grille toward you (slightly tilted) and lift it straight upward. Screw 1. To remove the sensor, housing connect, earth conductor & step motor conductor with sensor holder, Motor, Evaporator & P.C.B. Display P.C.B Conductor Sensor Conductor Motor Conductor Earth Conductor Step Motor Conductor Service Manual 55 Disassembly of the parts (Indoor unit) 2. To remove the Control Box. • Remove securing screws. • Pull the control box out from the chassis carefully. 3. To remove the Discharge Grille. • Unhook the discharge grille and pull the discharge grille out from the chassis carefully. 4. To remove the Evaporator. • Remove 3 screws securing the evaporator(at the left 2EA in the Eva Holder, at the right 1EA). 56 Multi Air Conditioner • Unhook the tab on the right inside of the chassis at the same time, slightly pull the evaporator toward you until the tab is clear of the slot. 5. To remove the Motor Cover • Remove 2 securing screw. • Pull the motor cover out from the chassis carefully. Motor cover 6. To remove the Cross-Flow Fan • Loosen the screw securing the cross-flow fan to the fan motor (do not remove). • Lift up the right side of the cross-flow fan and the fan motor, separate the fan motor from the cross-flow fan. • Remove the left end of the cross-flow fan from the self-aligning bearing. Service Manual 57 Exploded View and Replacement Parts List Exploded View and Replacement Parts List 1. Indoor Unit L2NH122GHL0, L2NC122GHL0 135316 152313 135314 152302 733010 131410 359011 342800 159830 159901 268712 346810 35211B 135516 354212 263230 352150 135311 268715 146811 268716 267110 249951 58 Multi Air Conditioner W0CZZ Exploded View and Replacement Parts List PART No. LOCATION No. DESCRIPTION REMARKS L2NC122GHL0 L2NH122GHL0 131410 CHASSIS ASSEMBLY 3141A20005B 3141A20005B R 135311 GRILLE ASSEMBLY, DISCHARGE(INDOOR) 3531A10192G 3531A10192D R 135316 GRILLE ASSEMBLY, FRONT(INDOOR) 3531A21018D 3531A21018K R 135314 GRILLE ASSEMBLY, INLET SUB 3530A10079A 3530A10079A R 135516 COVER ASSEMBLY, MOTOR 3551A20050W 3551A20050A R 146811 MOTOR ASSEMBLY, STEP 4681A20055A 4681A20055A R 152302 FILTER(MECH), A/C 5230A20014C 5230A20014C R 159830 AIR CLEANER ASSEMBLY 5983A10006U 5983A10006U R 159901 VANE, HORIZONTAL 5990A20007A 5990A20007A R 249951 CONTROL BOX ASSEMBLY, INDOOR 4995A20213C 4995A10072D R 263230 THERMISTOR ASSEMBLY 6323A20004A 6323A20004A R 267110 REMOTE CONTROLLER ASSY 6711A20069B 6711A20069C R 268712 PWB(PCB) ASSEMBLY, DISPLAY 6871A20227D 6871A20194A R 268715 PWB(PCB) ASSEMBLY, MAIN(AC) 6871A20239A 6871A20267A R 268716 PWB(PCB) ASSEMBLY, MAIN(DC) 6871A20229K 6871A20266A R 342800 BEARING 4280A20004A 4280A20004A R 346810 MOTOR ASSEMBLY, INDOOR 4681A20048D 4681A20048D R 35211B TUBE ASSEMBLY, TUBING 5211AR7066N 5211AR7066Y R 352150 HOSE ASSEMBLY, DRAIN 5251AR2575F 5251AR2575F R 354212 EVAPORATOR ASSEMBLY, FINAL 5421A20087B 5421A20087E R 359011 FAN ASSEMBLY, CROSS FLOW 5901A20007A 5901A20007A R 733010 PLATE ASSEMBLY, INSTALL 1H00843A 1H00843A R W0CZZ CAPACITOR DRAWING 3H01487A 3H01487A R NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request. (GCSC WEBSITE http://[email protected]) Service Manual 59 437210 435311 435512 60 Multi Air Conditioner 559010 349600 430410 447910 546810 W0CZZ-2 W0CZZ-1 554030 554160 649950 435511 137213 552203-2 552203-3 552203-1 Exploded View and Replacement Parts List 2. Outdoor Unit 2-1. L2UC242GL0 Exploded View and Replacement Parts List LOCATION No. PART No. DESCRIPTION REMARKS L2UC242GL0 137213 PANEL ASSY, REAR 3720AP0003F R 430410 BASE ASSY, OUTDOOR 3041AP2741G R 435311 GRILLE ASSY, DISCHARGE(OUTDOOR) 3530A20007B R 435511 COVER ASSY, CONTROL(OUTDOOR) 3551A20076C R 435512 COVER ASSY, TOP(OUTDOOR) 3H03266K R 437210 PANEL ASSY, FRONT SUB 3721A20005P R 447910 BARRIER ASSY, OUTDOOR 4791A30004K R 546810 MOTOR ASSY, AC 4681A20008D R 349600 MOUNT, MOTOR 4960AP1361A R 552203-1 VALVE, SERVICE 2H01890P R 552203-2 VALVE, SERVICE 2H01890Q R 552203-3 VALVE, SERVICE 2H02479J R 554030 CONDENSER ASSY, BEND 5403A20072E R 554160 COMPRESSOR ASSY, SET 2520UKRK2BB R 559010 FAN ASSY, PROPELLER 1A00195B R 649950 CONTROL BOX ASSY, OUTDOOR 4995AP2615F R W0CZZ-1 CAPACITOR, DRAWING 6120AR2194D R W0CZZ-2 CAPACITOR, DRAWING 2A00986G R NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request. (GCSC WEBSITE http://[email protected]) Service Manual 61 437210 435311 435512 62 Multi Air Conditioner 559010 349600 430410 447910 546810 561410-2 263230 554160 649950 552202 137213-1 268711 561410-1 W0CZZ-1 W0CZZ-2 554030 435511 437212 552203-2 552203-3 552203-1 137213-2 Exploded View and Replacement Parts List 2-2. L2UH242GL0 Exploded View and Replacement Parts List LOCATION No. PART No. DESCRIPTION REMARKS L2UH242GL0 137213-1 PANEL ASSY, SIDE-L 1A00201D R 137213-2 PANEL ASSY, SIDE-R 3A02284M R 437212 GRILLE, REAR 1A00207B R 268711 PWB(PCB)ASSY, MAIN(OUTDOOR) 6871A20273A R 430410 BASE ASSY, OUTDOOR 3041AP2741G R 435311 GRILLE ASSY, DISCHARGE(OUTDOOR) 3530A20007J R 435511 COVER ASSY, CONTROL(OUTDOOR) 3551A20076E R 437210 PANEL ASSY, FRONT SUB 3721A20004L R 447910 BARRIER ASSY, OUTDOOR 4791A30004C R 546810 MOTOR ASSY, AC 4681A20008D R 349600 MOUNT, MOTOR 4960AP1361A R 552203-1 VALVE, SERVICE 2H01890P R 552203-2 VALVE, SERVICE 2H01890Q R 552203-3 VALVE, SERVICE 2H02479J R 554030 CONDENSER ASSY, BEND 5403A20072X R 554160 COMPRESSOR ASSY, SET 2520UKRK2BB R 559010 FAN ASSY, PROPELLER 1A00195B R 561410-1 COIL ASSY, REVERSING 6141AR3509T R 561410-2 COIL ASSY, REVERSING 6141AR3509S R CONTROL BOX ASSY, OUTDOOR 4995A10071A R W0CZZ-1 CAPACITOR, DRAWING 6120AR2194D R W0CZZ-2 CAPACITOR, DRAWING 2A00986G R 435512 COVER ASSY, TOP(OUTDOOR) 3H03266L R 263230 THERMISTOR ASSEMBLY 6323A20002A R 552202 VALVE, REVERSING 5220AR3084A R 649950 NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request. (GCSC WEBSITE http://[email protected]) Service Manual 63 P/No.: 3828A20156N January, 2005 Printed in Korea