TROUBLESHOOTING Diagnostic Chart (for 12k Models) If, after energizing the unit, no indicator is lit and the unit cannot be operated, see the following chart. Be sure all the wires (including power wires and connection wires) No are OK Yes Install good ones Check for AC (208-230V) power supply outputs to outdoor control board Yes Check if AC (208-230V) exists at primary coil No of transformer (18K & 24K models only) Outdoor control board is Defective Yes Check if AC 12V and AC 35V (+5%) exist at secondary coil of transformer in the outdoor control board No Take off the secondary plug of transformer, and then check if AC Yes 12V and AC 35V (+5%) exist at secondary coil of transformer Yes Outdoor control board is Defective No Transformer is defective Check if DC 35V exists between 2 & 3 on the indoor terminal and DC 12V between 3 & 4 No Yes Check if DC 35V exists at CN6 and 12V at CN3 No Indoor control board is Defective Yes Uncertain problem on Indoor control board. Change it & check again. 21