Main Components
new refrigeration cycle. To maintain the correct refrigerant discharge pressure, the speed of the
motor fan is controlled (on ---off or proportional mode).
Shut---off valves are provided as standard to assist with routine maintenance.
The compressor has a built---in non ---return valve to avoid return of liquid refrigerant from the
condenser in summertime, thus protecting the compressor from undesired refrigerant slugging
during the start up. A second non ---return valve is recommended to avoid --- in wintertime --refrigerant migration from the liquid pipes and the receiver to the condenser, that should be
responsible of low pressure intervention at the start---up of compressor.
For safety reason, a relief valve is installed on the liquid receiver; this valve is equipped with flanged
connections so that the refrigerant may be discharged to the outside.
External air---cooled condenser (2)
The units may be connected with a wide range of our condensers in standard or low noise version.
For technical data and performance, refer to the relevant technical documentation. Chap. 8 gives
the recommended matching condenser for XDFN units as a function of outdoor air temperature.
Note 1. Units and external condensers are supplied separately.
Note 2. The room unit refrigeration circuit is pressurised with helium at 3 bar and the condenser
refrigeration circuit at 2 bar with dry air.
Note 3. The customer is responsible for making connections between the Unit and the external
condenser and for charging with refrigerant (standard R407C) and oil, when request.
Full instructions for these operations are given in the Service Manual.
4.1.4
Version W
Direct expansion units with water ---cooled condenser
Refrigeration circuit
All models are provided with a single refrigeration circuit. The compressor pumps the hot gaseous
refrigerant into a water ---cooled condenser. The liquefied refrigerant arrives to a liquid receiver that
ensures a constant and even refrigerant flow to the thermostatic expansion valve and then arrives
to the evaporator. Here the refrigerant, thanks to the heat --- exchanged with the room air moved by
the fan --- evaporates and returns to the compressor; from this, the refrigerant begins a new
refrigeration cycle.
Shut---off valves are provided as standard to assist with routine maintenance.
The compressor has a built---in non ---return valve to avoid return of liquid refrigerant from the
condenser, thus protecting the compressor from undesirable refrigerant slugging during the start
up. A second non ---return valve is recommended to avoid refrigerant migration from the liquid pipes
and the receiver to the condenser, that should be responsible of high pressure intervention at the
start---up of compressor.
For safety reason, a relief valve is installed on the liquid receiver; this valve is equipped with flanged
connections so that the refrigerant may be discharged to the outside.
Water---cooled condenser
These units are provided with one very efficient stainless steel brazed ---plate water ---cooled
condenser . The condenser is fitted with an head ---pressure regulating valve for the automatic
control of condensing pressure.
The units operate with mains water or closed circuit with an external Dry Cooler. When operating
in a closed circuit, to avoid undesired ice formation in wintertime, it is advisable to use water/glycol
mixture: refer to Chap. 8 for the percentages to be used at minimum ambient temperatures. Dry
Coolers are available as an option; water ---glycol mixture and circulation pump(s) are normally
supplied by others.
If mains water is used, a mechanical filter must be fitted in the water circuit to protect the plate
condenser (for other information see the Service Manual).
To reduce water and energy consumption (pump), it’s advisable to adopt a cooling water control
valve (by the user), able to stop water feeding when unit is off.
Unit microprocessor control gives a 24V contact (10VA max, please refer to the relevant Wiring
Diagram, 58 and G terminals) to drive that valve.
Note. The water ---cooled Himod versions are filled with the complete charge of the requested
refrigerant (standard R407C).