9. AC Electrical Connections 9.6 8-2010 Grounding The following is a brief description of system and equipment grounding of permanently installed AC generators within a facility wiring system. NOTE: It is important to follow the requirements of the local electrical code. Figure 15 and Figure 16 illustrate typical system grounding for a 3-pole and a 4-pole Automatic Transfer Switch (ATS). In the 3-pole ATS, note that the generator neutral is connected to the ATS and is NOT bonded to ground at the generator. In the 4-pole ATS system, a grounding electrode conductor and a bonding jumper are used to connect the generator neutral to ground. Make sure the generator set is grounded to earth in one location only. On generator sets without a circuit breaker, ground to the point indicated on the top of the generator. On generator sets with circuit breakers, use the ground lug provided in the circuit breaker box. WARNING: Electric current can cause severe personal injury or death. Bonding and grounding must be done properly. All metallic parts that could become energized under abnormal conditions must be properly grounded. No. Description 1 Service Entrance 2 3-Pole ATS 3 Generator Set 4 Load FIGURE 15. 44 TYPICAL SYSTEM - THREE-PHASE, FOUR WIRE UTILITY, THREE-POLE ATS A030G175 (Issue 3)