Download Inst Manual HD
Transcript
INSTALLATION 10. Do NOT use dampers or other devices in the vent or combustion air pipes. 11. Precautions must be taken to prevent degradation of building materials by flue products. 12. Single wall vent pipe must not pass through any unoccupied attic, inside wall, concealed space, or floor. 13. All vertically vented heaters that are category I must be connected to a factory built chimney or vent complying with a recognized standard, or a masonry (or concrete) lined chimney with a material acceptable to the authority having jurisdiction. Venting into an unlined masonry chimney is not permitted. Refer to the National Fuel Gas Code for common venting. 14. The outlet of the vent should extend as shown in Figure 6.3 and Table 6.1 if the following conditions are met: Vent diameter is less than 12", vent is of double wall construction and is a listed product, and the vent does not terminate within 8’ of a vertical wall or similar obstruction. For vents that have a diameter of 12" or larger, constructed of single wall, or terminate within 8' of a vertical wall or similar obstruction, the vent pipe shall extend at least 2' higher than any portion of a building within a horizontal distance of 10’ (refer to Figure 6.2). 15. The vent system exhaust shall terminate at least 3’ above any forced air inlet located within 10’, and at least 4’ below, 4’ horizontally from, or 1’ above any door, window, or gravity air inlet into any building and 2’ from wall or adjoining building. The bottom of the vent terminal shall be located above the snow line or at least 1’ above grade; whichever is greater. When located adjacent to public walkways the vent system shall terminate not less than 7’ above grade. 16. A minimum of 4’ horizontal terminal clearance (6’ for Canada) from gas and electric meters, regulators, and relief equipment is required. The vent terminal shall not terminate closer than 2’ to adjacent buildings. 17. Use an approved vent terminal to reduce down drafts and moisture in the vent. Table 6.1 Minimum Height from Roof to Lowest Discharge Opening Rise X (in) 0-6 6-7 7-8 8-9 9-10 10-11 11-12 12-14 14-16 16-18 18-20 20-21 Roof Pitch Flat to 6/12 6/12 to 7/12 7/12 to 8/12 8/12 to 9/12 9/12 to 10/12 10/12 to 11/12 11/12 to 12/12 12/12 to 14/12 14/12 to 16/12 16/12 to 18/12 18/12 to 20/12 20/12 to 21/12 ➀ Size according to expected snow depth. Figure 6.2 Vertical Venting Through Flat Roof 8' Min Listed Terminal 2' Min 5' Min 4" Min Drip Leg Downward Slope 1/4" towards drip leg. Figure 6.1 Venting Through Combustible Wall or Roof 12" Min Double Wall Vent Pipe ➀ Single Wall Vent Pipe Listed Terminal Flashing Min Height H (ft) ➀ 1.00 1.25 1.50 2.00 2.50 3.25 4.00 5.00 6.00 7.00 7.50 8.00 Listed Terminal Figure 6.3 Vertical Venting Through Sloped Roof Listed Terminal Flashing X H Listed Thimble Clearance Specified by Type B Vent Mfg. 12 Roof Pitch is x/12 Single Wall Double Wall Specified Terminal Single Wall Vent Pipe Terminating with Double wall vent pipe. ➁ Clearance Specified by Type B Vent Mfg. 4" Min Single Wall Downward Slope 1/4" towards drip leg. Specified Terminal Single Wall Vent Pipe Drip Leg Listed Thimble ➀ 6 See Instructions for attaching single wall pipe to double wall pipe (page 6) 6-576.5 12" Min