AirEx sens sup LO
Warning
Description
Cause
Trouble
shooting
Controller Internal Voltage Reference Fault
Indication of controller internal voltage reference fault
Possible causes:
•
Defect power supply for controller PCB.
•
Defect sensor pulling power supply down.
•
Defect controller PCB.
Accompanied alarms:
•
There may be sensor alarms, AL 3XX.
•
AL 801 will be activated during FT- or PTI test.
Trouble shooting:
1) Check if there are other active (sensor) alarms.
Clear these alarms first using their trouble shooting.
for more than 3 sec.
2) Access the “special menu” by pressing
Scroll down until you see the label “U AirEx” in the display.
The value of “U AirEx“ should be in the range between 4.80 and
5.05V DC.
3) While displaying “U AirEx“, remove the connector at AirEx
potentiometer.
−
If “U AirEx“ is now inside the correct above range (4.80 – 5.05V
DC), the AirEx potentiometer is defect.
Replace the AirEx potentiometer
−
If “U AirEx” is still outside the above range, proceed to next step.
4) While displaying “U AirEx“, disconnect “AirEx” from the terminals
according to wiring schematics inside in the control cabinet.
Criteria
Controller
action
−
If “U AirEx” is now inside the above range the cable for “AirEx” is
defect. Mount connector correctly or replace connector cable for
“AirEx”.
−
If “U AirEx” is still outside, correct the above range. The controller
PCB is defect.
Replace the controller door.
Reference voltage AirEx below 4.80V DC
None