Download Model 8680 SureFlow Adaptive Offset Controller Operation
Transcript
SETPOINTS MENU (continued) SOFTWARE NAME MIN EXH SET MINIMUM EXHAUST FLOW SET POINT ITEM DESCRIPTION The MIN EXH SET item sets the minimum general exhaust air flow out of the laboratory. The controller will not allow the general exhaust air damper to close further than the MIN EXH SET flow set point. NOTE: This item requires a TSI compatible flow station and control damper to be mounted in the general exhaust duct. ITEM RANGE DEFAULT (bold) Pressure based flow stations 0 - 2832 ft/min (0 - 14.4 m/s) x duct area in square feet (ft2): square meters (m2). Linear based flow stations 0 to TOP VELOCITY times the duct area in square feet (ft2): square meters (m2). 0 TEMP LOW TEMPERATURE COOLING The TEMP LOW item determines when the supply air changes from ventilation control mode (VENT MIN SET) to cooling temperature control mode (TEMP MIN SET). Off, 0-10 VDC. Off When the thermostat signal drops below the TEMP LOW voltage set point, the TEMP MIN SET is the supply air minimum (VENT MIN SET is overruled). Zero volts equates to maximum cooling. WIRING: The thermostat is connected to the temp input (pins 23 & 24, DIM). The 0-5 or 0-10 VDC thermostat signal is continuously monitored by the AOC. TEMP HIGH TEMPERATURE HEATING The TEMP HIGH determines when the supply air changes from ventilation control mode (VENT MIN SET) to temperature heating mode (TEMP MIN SET). Off, 0-10 VDC Off When the thermostat signal is greater than the TEMP HIGH voltage set point, the TEMP MIN SET is the supply air minimum (VENT MIN SET is overruled). If TEMP HIGH is programmed to be off, the supply air remains in ventilation mode when heating is required. 5 (0-5 VDC) or 10 volts equates to maximum heating. WIRING: The thermostat is connected to the temp input (pins 23 & 24, DIM). The 0-5 or 0-10 VDC thermostat signal is continuously monitored by the AOC. MIN OFFSET MINIMUM FLOW OFFSET The MIN OFFSET item sets the minimum air flow offset between total exhaust flow (fume hood, general exhaust, other exhaust) and total supply flow. Technical Section - 10,000 to 10,000 CFM 0 15