CONFIGURE MENU SOFTWARE NAME DISPLAY AVG DISPLAY AVERAGE UNITS ITEM DESCRIPTION The DISPLAY AVG item selects the display’s averaging period. The display averaging period is the length of time the room pressure has been averaged before being displayed. The DISPLAY AVG item value may be set between 0.75 and 40 seconds. The higher the averaging value, the more stable the display. The UNITS item selects the unit of measure that the DIM displays all values (except calibration span). These units display for all menu items set points, alarms, flows, etc.. ITEM RANGE DEFAULT (bold) 0.75, 1, 2, 3, 5, 10, 20 or 40 seconds 20 seconds FT/MIN, m/s, "H2O Pa, mm H2O "H2O ROOM VOLUME The ROOM VOLUME item is used to input the volume of the laboratory. The laboratory volume is needed to calculate ACPH (air changes per hour). If the DIM displays English units, area must be entered in cubic feet. If metric units are displayed area must be entered in cubic meters. 0 - 100,000 cubic feet (0 - 3000 cubic meters) 0 The DIM does not compute volume. The volume must be first calculated and then entered into the DIM. EXH CONFIG GENERAL EXHAUST DUCT CONFIGURATION The EXH CONFIG menu item determines the exhaust configuration. If the general exhaust duct is separate from the total exhaust select SEPARATE (left side of Figure 6). If the general exhaust duct is part of the total exhaust select COMBINED (right side of Figure 6). The correct configuration is required for the control algorithm to function correctly. SEPARATE or COMBINED SEPARATE Figure 6: Exhaust Configuration ACCESS CODE END OF MENU 20 The ACCESS CODE item selects whether an access code (pass code) is required to enter the menu. The ACCESS CODE item prevents unauthorized access to a menu. If the ACCESS CODE is ON a code is required before the menu can be entered. Conversely if the ACCESS CODE is OFF no code is required to enter the menu. ON or OFF OFF The END OF MENU item informs you that the end of a menu has been reached. You can either scroll back up the menu to make changes, or press the SELECT or MENU key to exit out of the menu. Part Two