Download Section 1.0 - GE Healthcare
Transcript
OPTIMA CT680 SERIES INSTALLATION MANUAL GE COMPANY DIRECTION 5472001-1EN, REVISION 2 3.7 A1 Breaker NOTICE • All sites must have a main disconnect with Lockout/Tagout capability. • Non GE-supplied breakers must have/provide under-voltage protection. For more information, refer to the Pre-Installation Manual for this system. • A LICENSED ELECTRICIAN shall install and make connections inside the main disconnect. A1 Breaker UPS North America(440V or 460-480V) E4502AB Optional Partial UPS Kit B7999ZA 1 – Pos. Subsystems Lock-out and tag-out the A1 breaker now. Europe and Asia 4(380-400V or 420V): E4502AC Table 1-1 Figure 1-1 Sample A1 Breaker 3.7.1 Installation Conditions 1.) A Final Site Print is required. Contact your PMI for a final site print. 2.) The room size must match the print. Measure the room size. If it does not match the stated size, and is smaller, then check all clearances. Service clearances MUST be met to continue. 3.) A customer Anchoring Plan is required if there is anything other than a 101.6 mm (4 in.) (minimum) concrete floor. GE employees shall only install the anchors supplied with this system. 4.) Complete this section on the GE Form e4879. 5.) Do not start the installation process if the site is under construction: - In the room - In the scan area - In addition, the radiology suite at such a site will REMAIN in a dust-free, occupancy-ready state after delivery and throughout the remaining construction phase. Chapter 1 - Position Subsystems Page 33