RXB PLUS ROTARY SCREW COMPRESSOR UNITS OPERATION COMPRESSOR HYDRAULIC SYSTEM S70-101 IOM Page 31 FUNCTIONAL CHECK OF THE COMPRESSOR VOLUME RATIO CONTROL (Vi) OPERATION The compressor hydraulic system moves the movable slide valve (MSV) to load and unload the compressor. It also moves the movable slide stop (MSS) to increase or decrease the compressor’s volume ratio (Vi). 1. Remove the slide valve potentiometer cover located on the outlet end of the compressor and secured by 4 cap screws. CAPACITY CONTROL 2. Push the Slide Stop Manual 2.2 Vi key on the micro keypad. COMPRESSOR LOADING: If the capacity control valve is mounted on the base, the compressor loads when MSV solenoid coil SV1 is energized. If the capacity control valve is mounted on the compressor, the compressor loads when MSV solenoid coil SV2 is energized. Oil flows from the solenoid valve through the needle valve (NV2) to compressor port 2, where it enters the load side of the slide valve piston. This equalizes the force on the slide valve piston and discharge pressure on the slide valve area loads the compressor. COMPRESSOR UNLOADING: If the capacity control valve is mounted on the base, the compressor unloads when MSV solenoid SV2 is energized. If the capacity control valve is mounted on the compressor, the compressor unloads when MSV solenoid coil SV2 is energized. Oil is allowed to flow from compressor port 2 through the needle valve to the MSV solenoid. This allows discharge pressure on the slide valve piston to unload the slide valve as the piston moves outward. ADJUSTMENT (Capacity Control): A needle valve (NV2) is provided to adjust slide valve travel time, preventing excessive slide valve “hunting”. NV2 should be adjusted to restrict oil flow to compressor port so that slide valve travel time from full load to full unload, or vice versa is a minimum of 30 seconds. 3. Push Manual Load on the Slide Valve Control and hold in the depressed position until the compressor is fully loaded. 4. Remove the Capacity Position Potentiometer which is secured by 2 bolts. This will expose the indicator rod which protrudes from the indicator rod guide. 5. In the 2.2 Vi position, the rod should extend from the guide the amount shown in the Indicator Rod Extension table. 6. With the slide valve fully loaded, depress the manual 3.5 Vi key. Movement of the indicator rod should occur as the Vi is changed so that the rod extension corresponds to the table. 7. Reassemble the parts if the functional check is satisfactory. If the indicator rod does not move to the proper position as the table indicates, then the compressor is not changing Vi in either manual or optional automatic operation. This would result in higher compressor motor horsepower consumption and possibly high oil temperature. The problem would be caused by a malfunction of either solenoid valve 3SOL or 4SOL, or the solenoid coil. Replace as required. INDICATOR ROD EXTENSION (in.) NOTE: A change in operating conditions may require readjustment of Slide Valve travel time (NV). VOLUMIZER®II Vi CONTROL Solenoid valves 3 and 4 control the Vi Ratio. Oil is internally ported to move the Movable Slide Stop. Vi SOL-3 (TOP) SOL-4 (BOTTOM) 2.2 3.5 5.0 Energized De-energized De-energized Energized Energized De-energized CAPACITY CONTROL VALVE MOUNTED ON BASE Vi POSITION RXB 12, 15, & 19 RXB 24, 30, 39, & 50 2.2 3.5 5.0 .412 / .454 .297 / .339 .235 / .277 .434 / .474 .319 / .359 .258 / .298 CAPACITY CONTROL VALVE ON COMPRESSOR