Download 1794-6.5.7, Thermocouple/Millivolt Input Module, User Manual
Transcript
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter Defaults 5–7 Each I/O module has default values associated with it. At default, each module will generate inputs/status and expect outputs/configuration. Module Defaults for: Catalog Number 1794-IT8 Description 8 Thermocouple Input Factory Defaults Real Time Size Input Default Output Default Input Default Output Default 11 4 10 0 Factory defaults are the values assigned by the adapter when you: • first power up the system, and • no previous stored settings have been applied. For analog modules, the defaults reflect the actual number of input words/output words. For example, for the 8 thermocouple input analog module, you have 11 input words, and 4 output words. You can change the I/O data size for a module by reducing the number of words mapped into the adapter module, as shown in “real time sizes.” Real time sizes are the settings that provide optimal real time data to the adapter module. Analog modules have 15 words assigned to them. This is divided into input words/output words. You can reduce the I/O data size to fewer words to increase data transfer over the backplane. For example, an 8 thermocouple input module has 11 words input/4 words output with factory default. You can reduce the write words to 0, thus eliminating the configuration setting and unused words. And you can reduce the read words to 10 by eliminating the calibration status words. More For information on using DeviceNetManager software to configure your adapter, refer to the DeviceNetManager Software User Manual, publication 1787-6.5.3. Publication 1794-6.5.7 – April 1997