Download SERVICE MANUAL

Transcript
Fig. 12 --- Suggested refrigerant connections (HPSCxxL + HPSE)
Gas pipeline (Sloping 1%)
HPSC
(External Unit)
Liquid pipeline
50 m max. horizontal equivalent length
HPSE
(Internal Unit)
Syphons (obligatory)
Gas pipeline
(Sloping 1%)
HPSE
(Internal Unit)
Liquid pipeline
3 m max. vertical distance
HPSC
(External Unit)
1.5 m max. vertical
distance between
two syphons
Gas pipeline
(Sloping 1%)
30 m max. horizontal equivalent length
5 m max. vertical
distance between
two syphons
HPSE
(Internal Unit)
Gas pipeline
(Sloping 1%)
HPSC
(External Unit)
Liquid pipeline
30 m max. horizontal equivalent length
pag. 38
15 m max. vertical distance
Gas pipeline
(Sloping 1%)