Installation of PC Central Controller Software
Defect
The specifications on the central controller screen is not
communicated to the indoor appear
Check method
• Operating the indoor units confirm the communication between the outdoor
units.
• If case there is non communication between indoor /outdoor then there is no
communication with the central controller.
• ADDRESS setting confirmation
• In case the same address has been assigned to more than 2 indoor units
then all indoor units will not appear on the central controller.
• When The registration of the central controller is different from the actual
product, the central controller will not recognize the respective indoor units.
• LAN Line connection confirmation confirm the LAN wire connection contact.
Installation Manual 41
ENGLISH
• Double click the Service manager on the screen to stop the program
execution . Then again press the start button