Download Motion Control - Service, Support
Transcript
08.2008 Technical Data Derating curves Permissible rated input voltage in % according to VDE 0110 / IEC 664-1 (not required by UL / CSA) 100 75 50 0 1000 2000 3000 4000 Height above sea level in m Permissible rated current in % 100 Height [m] Derating factor K1 1000 1.0 2000 0.9 3000 0.845 4000 0.8 100 Temp [°C] Derating factor K2 75 50 0.879 45 1.0 50 40 1.125 35 1.25 * 30 1.375 * 25 1.5 * 90 80 70 60 0 1000 2000 3000 4000 Height above sea level in m Permissible rated current in % 25 0 0 10 20 30 40 50 Coolant temperature in °C *See note below Derating for units of ≥ 22 kW Permissible rated current in % 100 Pulse Derating frequency factor K 3 kHz 75 50 0 2 Fig. 11-1 4 6 6 1.00 7 0.95 8 0.90 9 0.85 10 0.80 8 10 12 14 16 18 Pulse frequency Derating curves Siemens AG 6SE7087-8KP50 SIMOVERT MASTERDRIVES Operating Instructions 11-3