Download DL8000 Preset Controller

Transcript
Form A6252
July 2010
Safe Use Instructions – DL8000
DL8000 Preset Controller
When installing units in a hazardous area, make sure
all installation components selected are labeled for
use in such areas. Installation and maintenance must
be performed only when the area is known to be nonhazardous. Installation or maintenance in a hazardous
area could result in personal injury or property
damage.
Always turn off the power to the DL8000 before you
attempt any type of wiring. Wiring of powered
equipment could result in personal injury or property
damage.
Use this safe use instructions (SUI) document with the
DL8000 Preset Controller Instruction Manual (Form
A6212). For full cautions and descriptions of installation
and troubleshooting procedures, refer to the manual. If
you require training for this product, contact your local
sales office.
The DL8000 Preset Controller (or “DL8000”) with CE
marking may be ordered with any of the optional
communications or I/O modules listed in the DL8000
Preset Specification Sheet (DL8000).
Declaration of Conformity
Hereby, Remote Automation Solutions declares that the
DL8000 products are in compliance with the essential
requirements and other relevant provisions of European
Directives 2004/108/EC (EMC), 1994/9/EC (ATEX), and
2004/22/EC (MID).
MID Special Conditions for Use
ƒ
The minimum measured quantity shall be inscribed
on the calculating and indicating device or on a
separate plate in the direct vicinity of the display.
ƒ
In installations where more than one measurement
transducer is applied, an identification of the
connected measurement transducer shall also be
applied on or in the vicinity of the calculating and
indicating device.
ƒ
In systems where volume conversion is carried out,
a description of the reference condition is applied on
or in the vicinity of the display.
ƒ
In case a printing device is connected, provide an
additional feedback from the printing device to the
calculating and indicating device for power-off
detection and paper-out detection.
Remote Automation Solutions
Website: www.EmersonProcess.com/Remote
To avoid circuit damage when working inside the unit,
use appropriate electrostatic discharge precautions,
such as wearing a grounded wrist strap.
Check the input power polarity before connecting
power to the DL8000.
Specifications
POWER
100 to 240 V ac (+10%/–15%), 50 to 60 Hz,
1-phase 30-watt nominal.
MATERIALS
Enclosure: IP66, weatherproof, corrosionresistant cast aluminum with stainless steel bolts.
Wire Channel Covers: Polypropylene Plastic.
Modules: Thermoplastic Polyester, solventresistant.
ENVIRONMENTAL
Temperature (operating):
–40°C to +65°C.
–20°C to +65°C (LCD display).
–25°C to +55°C (certified by NMI).
Temperature (storage, non-operating):
–30°C to +80°C.
Relative Humidity: IEC68-2-3; 5-95% noncondensing.
WEIGHT
34 kg for housing, backplane, and CPU.
APPROVALS
Evaluated to the following European
Standards (EMC):
EN 55011 (Emissions).
EN 61000-4-2 (Electrostatic Discharge
Immunity).
EN 61000-4-3 (Electromagnetic Field Immunity).
D301347X412
Figure 1. DL8000 Label